 E-51 Explicit 6-zone model without graphical display         12/13/99   

 SUPERBLOCK 1
      BLOCK 1
          UNIT  1     TYPE504 - Read inputs from a file                      

 SUPERBLOCK 2
      BLOCK 2
          UNIT  2     TYPE481 - E-51 supply fan static pressure control      
          UNIT  3     TYPE482 - E-51 flow difference control of return fan   
          UNIT  4     TYPE483 - E-51 return fan reset control                
          UNIT  5     TYPE484 - E-51 minimum outside air damper control      
          UNIT  6     TYPE485 - E-51 modulated mixed air damper control      
          UNIT  7     TYPE486 - E-51 supply air temperature control          
          UNIT  8     TYPE487 - E-51 economizer control                      
          UNIT  9     TYPE488 - E-51 low temperature control                 
          UNIT 10     TYPE489 - E-51 supply air temperature reset            
          UNIT 11     TYPE490 - VAV room temperature control with reheat     
          UNIT 12     TYPE490 - VAV room temperature control with reheat     
          UNIT 13     TYPE490 - VAV room temperature control with reheat     
          UNIT 14     TYPE490 - VAV room temperature control with reheat     
          UNIT 15     TYPE490 - VAV room temperature control with reheat     
          UNIT 16     TYPE490 - VAV room temperature control with reheat     

 SUPERBLOCK 3
      BLOCK 3
          UNIT 17     TYPE333 - Variable speed drive                         
          UNIT 18     TYPE333 - Variable speed drive                         
          UNIT 19     TYPE321 - Motor-driven actuator                        
          UNIT 20     TYPE321 - Motor-driven actuator                        
          UNIT 21     TYPE321 - Motor-driven actuator                        
          UNIT 22     TYPE321 - Motor-driven actuator                        
          UNIT 23     TYPE321 - Motor-driven actuator                        
          UNIT 24     TYPE321 - Motor-driven actuator                        
          UNIT 25     TYPE321 - Motor-driven actuator                        
          UNIT 26     TYPE321 - Motor-driven actuator                        
          UNIT 27     TYPE321 - Motor-driven actuator                        
          UNIT 28     TYPE321 - Motor-driven actuator                        
          UNIT 29     TYPE321 - Motor-driven actuator                        

 SUPERBLOCK 4
      BLOCK 4
          UNIT 30     TYPE327 - Mixing box with minimum outside air damper   
          UNIT 31     TYPE341 - Fluid resistance                             
          UNIT 32     TYPE350 - Fan or pump                                  
          UNIT 33     TYPE341 - Fluid resistance                             
          UNIT 34     TYPE346 - Asymmetric flow split                        
          UNIT 35     TYPE346 - Asymmetric flow split                        
          UNIT 36     TYPE346 - Asymmetric flow split                        
          UNIT 37     TYPE346 - Asymmetric flow split                        
          UNIT 38     TYPE346 - Asymmetric flow split                        
          UNIT 39     TYPE526 - Motorized pressure-independent VAV box       
          UNIT 40     TYPE526 - Motorized pressure-independent VAV box       
          UNIT 41     TYPE526 - Motorized pressure-independent VAV box       
          UNIT 42     TYPE526 - Motorized pressure-independent VAV box       
          UNIT 43     TYPE526 - Motorized pressure-independent VAV box       
          UNIT 44     TYPE525 - Motorized pressure-independent VAV box       
          UNIT 45     TYPE349 - Room air mass balance                        
          UNIT 46     TYPE349 - Room air mass balance                        
          UNIT 47     TYPE349 - Room air mass balance                        
          UNIT 48     TYPE349 - Room air mass balance                        
          UNIT 49     TYPE349 - Room air mass balance                        
          UNIT 50     TYPE349 - Room air mass balance                        
          UNIT 51     TYPE348 - Flow merge                                   
          UNIT 52     TYPE348 - Flow merge                                   
          UNIT 53     TYPE348 - Flow merge                                   
          UNIT 54     TYPE348 - Flow merge                                   
          UNIT 55     TYPE348 - Flow merge                                   
          UNIT 56     TYPE350 - Fan or pump                                  
          UNIT 57     TYPE341 - Fluid resistance                             

 SUPERBLOCK 5
      BLOCK 5
          UNIT 58     TYPE367 - Mixing of two moist air streams              
          UNIT 59     TYPE524 - Coil + three port valve, calculates flow     
          UNIT 60     TYPE366 - Ideal heating of fluid stream                
          UNIT 61     TYPE524 - Coil + three port valve, calculates flow     
          UNIT 62     TYPE524 - Coil + three port valve, calculates flow     
          UNIT 63     TYPE524 - Coil + three port valve, calculates flow     
          UNIT 64     TYPE524 - Coil + three port valve, calculates flow     
          UNIT 65     TYPE524 - Coil + three port valve, calculates flow     
          UNIT 66     TYPE524 - Coil + three port valve, calculates flow     
          UNIT 67     TYPE403 - Room with plenum and ducted return and interz
          UNIT 68     TYPE403 - Room with plenum and ducted return and interz
          UNIT 69     TYPE403 - Room with plenum and ducted return and interz
          UNIT 70     TYPE403 - Room with plenum and ducted return and interz
          UNIT 71     TYPE403 - Room with plenum and ducted return and interz
          UNIT 72     TYPE403 - Room with plenum and ducted return and interz
          UNIT 73     TYPE368 - Mixing of six moist air streams              
          UNIT 74     TYPE366 - Ideal heating of fluid stream                

 SUPERBLOCK 6
      BLOCK 6
          UNIT 75     TYPE 26 - CONTROL SIGNAL INVERTER                      

 SUPERBLOCK 7
      BLOCK 7
          UNIT 76     TYPE 26 - CONTROL SIGNAL INVERTER                      

 SUPERBLOCK 8
      BLOCK 8
          UNIT 77     TYPE301 - Temperature sensor                           
          UNIT 78     TYPE301 - Temperature sensor                           
          UNIT 79     TYPE301 - Temperature sensor                           
          UNIT 80     TYPE301 - Temperature sensor                           
          UNIT 81     TYPE301 - Temperature sensor                           
          UNIT 82     TYPE301 - Temperature sensor                           
          UNIT 83     TYPE301 - Temperature sensor                           
          UNIT 84     TYPE301 - Temperature sensor                           
          UNIT 85     TYPE301 - Temperature sensor                           
          UNIT 86     TYPE301 - Temperature sensor                           
          UNIT 87     TYPE303 - Flow rate sensor                             
          UNIT 88     TYPE303 - Flow rate sensor                             
          UNIT 89     TYPE305 - Static pressure sensor                       
          UNIT 90     TYPE302 - Humidity sensor                              
          UNIT 91     TYPE302 - Humidity sensor                              

 SUPERBLOCK 9
      BLOCK 9
          UNIT 92     TYPE 26 - CONTROL SIGNAL INVERTER                      

 SUPERBLOCK10
      BLOCK10
          UNIT 93     TYPE 26 - CONTROL SIGNAL INVERTER                      

 UNIT   1      TYPE 504
 Read inputs from a file                                                 

 1     INPUTS:
        CONTROL         76 - dummy - must not be CONTROL 0                     

 2     OUTPUTS:
        CONTROL          1 - simulation input 1                                
        CONTROL          2 - simulation input 2                                
        CONTROL          3 - simulation input 3                                
        CONTROL          4 - simulation input 4                                
        CONTROL          5 - simulation input 5                                
        CONTROL          6 - simulation input 6                                
        CONTROL          7 - simulation input 7                                
        CONTROL          8 - simulation input 8                                
        CONTROL          9 - simulation input 9                                
        CONTROL         10 - simulation input 10                               
        CONTROL         11 - simulation input 11                               
        CONTROL         12 - simulation input 12                               
        CONTROL         13 - simulation input 13                               
        CONTROL         14 - simulation input 14                               
        CONTROL         15 - simulation input 15                               
        CONTROL         16 - simulation input 16                               

 3     PARAMETERS:
           1.00000     file number (FILE=inputN.par, N > 0) (-)               
           2.50000     sample time (interval between reads) (s)               
           0.00000     real time scaling factor (0=no wait, 1=real time)      
           0.00000     text output to screen (0=no, 1=yes) (-)                
           3.00000     number of values to read (-)                           

 UNIT   2      TYPE 481
 E-51 supply fan static pressure control                                 

 1     INPUTS:
        CONTROL         65 - static pressure sensor                            
        CONTROL          3 - static pressure setpoint                          
        CONTROL          1 - supply fan status (1 = on, 0 = off)               
        CONTROL          2 - return fan status (1 = on, 0 = off)               

 2     OUTPUTS:
        CONTROL         23 - supply fan speed                                  

 3     PARAMETERS:
           1.16000     proportional band (kPa)                                
           16.0000     integral time (s)                                      
           0.00000     derivative time (s)                                    
           0.00000     deadband (KPa)                                         
          0.125000     high limit override proportional band (kPa)            
          0.623000     high limit override setpoint (KPa)                     
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
          0.700000     open loop supply fan speed (0-1) (-)                   
           2.50000     sampling interval (s)                                  
           1.00000     controller number (parameters in file contN.par) (-)   

 UNIT   3      TYPE 482
 E-51 flow difference control of return fan                              

 1     INPUTS:
        CONTROL         63 - supply air volume flow rate sensor                
        CONTROL         64 - return air volume flow rate sensor                
        CONTROL          1 - supply fan status (1 = on, 0 = off)               
        CONTROL          2 - return fan status (1 = on, 0 = off)               
        CONTROL         17 - setpoint for flow rate difference                 

 2     OUTPUTS:
        CONTROL         24 - return fan speed (0-1)                            

 3     PARAMETERS:
          -8.66000     proportional band (m3/s) (-)                           
           50.0000     integral time (s)                                      
           0.00000     derivative time (s)                                    
          0.944000E-01 deadband (m3/s)                                        
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
          0.950000     open loop return fan speed (0-1) (-)                   
           2.50000     sampling interval (s)                                  
           2.00000     controller number (parameters in file contN.par) (-)   

 UNIT   4      TYPE 483
 E-51 return fan reset control                                           

 1     INPUTS:
        CONTROL         18 - minimum outside air damper position (open=TRUE)   

 2     OUTPUTS:
        CONTROL         17 - return fan controller setpoint                    

 3     PARAMETERS:
          0.472000     return fan setpoint when min OA damper open (m3/s)     
           2.50000     sampling interval (s)                                  
           3.00000     controller number (parameters in file contN.par) (-)   

 UNIT   5      TYPE 484
 E-51 minimum outside air damper control                                 

 1     INPUTS:
        CONTROL         61 - supply air temperature sensor                     
        CONTROL         60 - outside air temperature sensor                    
        CONTROL          1 - supply fan status (1 = on, 0 = off)               

 2     OUTPUTS:
        CONTROL         18 - minimum outside air damper position               

 3     PARAMETERS:
           4.44000     supply air temperature limit (C)                       
          -6.66000     outdoor air temperature limit (C)                      
           2.50000     sampling interval (s)                                  
           4.00000     controller number (parameters in file contN.par) (-)   

 UNIT   6      TYPE 485
 E-51 modulated mixed air damper control                                 

 1     INPUTS:
        CONTROL         68 - mixed air temperature sensor                      
        CONTROL         22 - mixing box cooling demand (0-1)                   
        CONTROL          1 - supply fan status (1 = on, 0 = off)               
        CONTROL         20 - low temperature override (1 = low temperature)    
        CONTROL         19 - economizer status (1 = OA enthalpy > RA enthalpy) 

 2     OUTPUTS:
        CONTROL         25 - outside air damper demanded position (0-1)        
        CONTROL         26 - return air damper demanded position (0-1)         
        CONTROL         27 - exhaust air damper demanded position (0-1)        

 3     PARAMETERS:
           4.44000     mixed air temperature setpoint (C)                     
          -3.89000     proportional band (K)                                  
           0.00000     integral time (s)                                      
           0.00000     derivative time (s)                                    
           0.00000     deadband (K)                                           
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
           1.00000     open loop outside air damper position (-)              
           0.00000     open loop return air damper position (-)               
           1.00000     open loop exhaust air damper position (-)              
           5.00000     sampling interval (s)                                  
           5.00000     controller number (parameters in file contN.par) (-)   

 UNIT   7      TYPE 486
 E-51 supply air temperature control                                     

 1     INPUTS:
        CONTROL         61 - supply air temperature sensor                     
        CONTROL          1 - supply fan status (1 = on, 0 = off)               
        CONTROL         20 - low temperature override signal (1=TRUE, 0=FALSE) 
        CONTROL         21 - supply air temperature setpoint                   

 2     OUTPUTS:
        CONTROL         22 - damper cooling demand (0-1)                       
        CONTROL         28 - cooling coil valve demand (0-1)                   

 3     PARAMETERS:
          -7.78000     proportional band (K)                                  
           125.000     integral time (s)                                      
           0.00000     derivative time (s)                                    
           1.00000     breakpoint between damper and cooling coil demand (0-2)
          0.220000     deadband (K)                                           
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
           0.00000     manual cooling coil demand (0-1) (-)                   
           5.00000     sampling interval (s)                                  
           6.00000     controller number (parameters in file contN.par) (-)   

 UNIT   8      TYPE 487
 E-51 economizer control                                                 

 1     INPUTS:
        CONTROL         60 - outdoor air temperature sensor                    
        CONTROL         66 - outdoor air relative humidity sensor (0-1)        
        CONTROL         62 - return air temperature sensor                     
        CONTROL         67 - return air relative humidity sensor (0-1)         

 2     OUTPUTS:
        CONTROL         19 - economizer status (1 = OA enthalpy > RA enthalpy) 

 3     PARAMETERS:
           5.00000     sampling interval (s)                                  

 UNIT   9      TYPE 488
 E-51 low temperature control                                            

 1     INPUTS:
        CONTROL         61 - supply air temperature sensor                     
        CONTROL         60 - outdoor air temperature sensor                    
        CONTROL          1 - supply fan status (1 = on, 0 = off)               

 2     OUTPUTS:
        CONTROL         20 - low temperature override signal                   

 3     PARAMETERS:
           4.44000     supply air temperature limit (C)                       
          -6.66000     outdoor air temperature limit (C)                      
           5.00000     sampling interval (s)                                  
           8.00000     controller number (parameters in file contN.par) (-)   

 UNIT  10      TYPE 489
 E-51 supply air temperature reset                                       

 1     INPUTS:
        CONTROL         70 - temperature sensor in zone 1                      
        CONTROL         71 - temperature sensor in zone 2                      
        CONTROL         72 - temperature sensor in zone 3                      
        CONTROL         73 - temperature sensor in zone 4                      
        CONTROL         74 - temperature sensor in zone 5                      
        CONTROL         75 - temperature sensor in zone 6                      

 2     OUTPUTS:
        CONTROL         21 - supply air temperature setpoint                   

 3     PARAMETERS:
           22.2200     zone temperature setpoint (C)                          
           1.11000     proportional band (K)                                  
           0.00000     integral time (s)                                      
           18.3000     upper limit of the output (C)                          
           12.7000     lower limit of the output (C)                          
           15.5000     output at zero error (P), initial output (PI) (C)      
           0.00000     deadband (K)                                           
           6.00000     number of inputs (-)                                   
           5.00000     sampling interval (s)                                  
           9.00000     controller number (parameters in file contN.par) (-)   

 UNIT  11      TYPE 490
 VAV room temperature control with reheat                                

 1     INPUTS:
        CONTROL         70 - space temperature sensor                          
        CONTROL         61 - supply air temperature sensor                     
        CONTROL          1 - supply fan status (1 = on, 0 = off)               

 2     OUTPUTS:
        CONTROL         48 - normalised volumetric flow demand (0-1)           
        CONTROL         29 - reheat coil demand (0-1)                          
        CONTROL         54 - room demand (heating and cooling) (-1 - +1)       

 3     PARAMETERS:
           18.3300     heating setpoint for zone (C)                          
           22.2200     cooling setpoint for zone (C)                          
           5.00000     proportional band (K)                                  
           900.000     integral time (s)                                      
           0.00000     derivative time (s)                                    
           0.00000     breakpoint btwn damper and reheat coil signals (-1-+1) 
          0.400000     minimum turndown ratio (-)                             
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
           1.00000     open loop normalised volumetric flow demand (-)        
           0.00000     manual reheat coil demand (0-1) (-)                    
           5.00000     sampling interval (s)                                  
           13.0000     controller number (parameters in file contN.par) (-)   

 UNIT  12      TYPE 490
 VAV room temperature control with reheat                                

 1     INPUTS:
        CONTROL         71 - space temperature sensor                          
        CONTROL         61 - supply air temperature sensor                     
        CONTROL          1 - supply fan status (1 = on, 0 = off)               

 2     OUTPUTS:
        CONTROL         49 - normalised volumetric flow demand (0-1)           
        CONTROL         30 - reheat coil demand (0-1)                          
        CONTROL         55 - room demand (heating and cooling) (-1 - +1)       

 3     PARAMETERS:
           18.3300     heating setpoint for zone (C)                          
           22.2200     cooling setpoint for zone (C)                          
           5.00000     proportional band (K)                                  
           900.000     integral time (s)                                      
           0.00000     derivative time (s)                                    
           0.00000     breakpoint btwn damper and reheat coil signals (-1-+1) 
          0.400000     minimum turndown ratio (-)                             
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
           1.00000     open loop normalised volumetric flow demand (-)        
           0.00000     manual reheat coil demand (0-1) (-)                    
           5.00000     sampling interval (s)                                  
           15.0000     controller number (parameters in file contN.par) (-)   

 UNIT  13      TYPE 490
 VAV room temperature control with reheat                                

 1     INPUTS:
        CONTROL         72 - space temperature sensor                          
        CONTROL         61 - supply air temperature sensor                     
        CONTROL          1 - supply fan status (1 = on, 0 = off)               

 2     OUTPUTS:
        CONTROL         50 - normalised volumetric flow demand (0-1)           
        CONTROL         31 - reheat coil demand (0-1)                          
        CONTROL         56 - room demand (heating and cooling) (-1 - +1)       

 3     PARAMETERS:
           18.3300     heating setpoint for zone (C)                          
           22.2200     cooling setpoint for zone (C)                          
           5.00000     proportional band (K)                                  
           900.000     integral time (s)                                      
           0.00000     derivative time (s)                                    
           0.00000     breakpoint btwn damper and reheat coil signals (-1-+1) 
          0.400000     minimum turndown ratio (-)                             
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
           1.00000     open loop normalised volumetric flow demand (-)        
           0.00000     manual reheat coil demand (0-1) (-)                    
           5.00000     sampling interval (s)                                  
           11.0000     controller number (parameters in file contN.par) (-)   

 UNIT  14      TYPE 490
 VAV room temperature control with reheat                                

 1     INPUTS:
        CONTROL         73 - space temperature sensor                          
        CONTROL         61 - supply air temperature sensor                     
        CONTROL          1 - supply fan status (1 = on, 0 = off)               

 2     OUTPUTS:
        CONTROL         51 - normalised volumetric flow demand (0-1)           
        CONTROL         32 - reheat coil demand (0-1)                          
        CONTROL         57 - room demand (heating and cooling) (-1 - +1)       

 3     PARAMETERS:
           18.3300     heating setpoint for zone (C)                          
           22.2200     cooling setpoint for zone (C)                          
           5.00000     proportional band (K)                                  
           900.000     integral time (s)                                      
           0.00000     derivative time (s)                                    
           0.00000     breakpoint btwn damper and reheat coil signals (-1-+1) 
          0.400000     minimum turndown ratio (-)                             
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
           1.00000     open loop normalised volumetric flow demand (-)        
           0.00000     manual reheat coil demand (0-1) (-)                    
           5.00000     sampling interval (s)                                  
           14.0000     controller number (parameters in file contN.par) (-)   

 UNIT  15      TYPE 490
 VAV room temperature control with reheat                                

 1     INPUTS:
        CONTROL         74 - space temperature sensor                          
        CONTROL         61 - supply air temperature sensor                     
        CONTROL          1 - supply fan status (1 = on, 0 = off)               

 2     OUTPUTS:
        CONTROL         52 - normalised volumetric flow demand (0-1)           
        CONTROL         33 - reheat coil demand (0-1)                          
        CONTROL         58 - room demand (heating and cooling) (-1 - +1)       

 3     PARAMETERS:
           18.3300     heating setpoint for zone (C)                          
           22.2200     cooling setpoint for zone (C)                          
           5.00000     proportional band (K)                                  
           900.000     integral time (s)                                      
           0.00000     derivative time (s)                                    
           0.00000     breakpoint btwn damper and reheat coil signals (-1-+1) 
          0.400000     minimum turndown ratio (-)                             
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
           1.00000     open loop normalised volumetric flow demand (-)        
           0.00000     manual reheat coil demand (0-1) (-)                    
           5.00000     sampling interval (s)                                  
           16.0000     controller number (parameters in file contN.par) (-)   

 UNIT  16      TYPE 490
 VAV room temperature control with reheat                                

 1     INPUTS:
        CONTROL         75 - space temperature sensor                          
        CONTROL         61 - supply air temperature sensor                     
        CONTROL          1 - supply fan status (1 = on, 0 = off)               

 2     OUTPUTS:
        CONTROL         53 - normalised volumetric flow demand (0-1)           
        CONTROL         34 - reheat coil demand (0-1)                          
        CONTROL         59 - room demand (heating and cooling) (-1 - +1)       

 3     PARAMETERS:
           18.3300     heating setpoint for zone (C)                          
           22.2200     cooling setpoint for zone (C)                          
           5.00000     proportional band (K)                                  
           900.000     integral time (s)                                      
           0.00000     derivative time (s)                                    
           0.00000     breakpoint btwn damper and reheat coil signals (-1-+1) 
          0.400000     minimum turndown ratio (-)                             
           1.00000     control mode (0=open loop, 1=closed loop) (-)          
           1.00000     open loop normalised volumetric flow demand (-)        
           0.00000     manual reheat coil demand (0-1) (-)                    
           5.00000     sampling interval (s)                                  
           12.0000     controller number (parameters in file contN.par) (-)   

 UNIT  17      TYPE 333
 Variable speed drive                                                    

 1     INPUTS:
        CONTROL         23 - demanded fractional speed                         

 2     OUTPUTS:
        OTHER            1 - actual rotation speed                             

 3     PARAMETERS:
           22.3330     maximum rotation speed (rev/s)                         
           30.0000     travel time (lim-lim) (s)                              

 UNIT  18      TYPE 333
 Variable speed drive                                                    

 1     INPUTS:
        CONTROL         24 - demanded fractional speed                         

 2     OUTPUTS:
        OTHER            2 - actual rotation speed                             

 3     PARAMETERS:
           8.00000     maximum rotation speed (rev/s)                         
           30.0000     travel time (lim-lim) (s)                              

 UNIT  19      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         18 - demanded position                                 

 2     OUTPUTS:
        CONTROL         37 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  20      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         25 - demanded position                                 

 2     OUTPUTS:
        CONTROL         38 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  21      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         26 - demanded position                                 

 2     OUTPUTS:
        CONTROL         39 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           1.00000     starting position (0-1)                                
           1.00000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  22      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         27 - demanded position                                 

 2     OUTPUTS:
        CONTROL         40 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  23      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         28 - demanded position                                 

 2     OUTPUTS:
        CONTROL         41 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  24      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         29 - demanded position                                 

 2     OUTPUTS:
        CONTROL         42 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  25      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         30 - demanded position                                 

 2     OUTPUTS:
        CONTROL         43 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  26      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         31 - demanded position                                 

 2     OUTPUTS:
        CONTROL         44 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  27      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         32 - demanded position                                 

 2     OUTPUTS:
        CONTROL         45 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  28      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         33 - demanded position                                 

 2     OUTPUTS:
        CONTROL         46 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  29      TYPE 321
 Motor-driven actuator                                                   

 1     INPUTS:
        CONTROL         34 - demanded position                                 

 2     OUTPUTS:
        CONTROL         47 - position of final control element                 
        CONTROL          0 - motor position                                    
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by finalcontrol element  

 3     PARAMETERS:
           1.00000     direction: 1=forward, -1=reverse, 0=stuck              
           0.00000     starting position (0-1)                                
           125.000     travel time (lim-lim) (s)                              
           0.00000     minimum change in demanded position for movement (-)   
           0.00000     hysteresis (-)                                         
           0.00000     crank travel angle (0 for linear) (deg)                
           1.00000     Upper limit of control element range on actuator scale 
           0.00000     Lower limit of control element range on actuator scale 

 UNIT  30      TYPE 327
 Mixing box with minimum outside air damper                              

 1     INPUTS:
        TEMPERATURE      1 - Outside air dry bulb temperature                  
        HUMIDITY         1 - Outside air humidity ratio                        
        TEMPERATURE     54 - Extract air dry bulb temperature                  
        HUMIDITY        16 - Extract air humidity ratio                        
        PRESSURE         1 - Outside air intake pressure                       
        PRESSURE        29 - Exhaust air outlet pressure                       
        PRESSURE         2 - Mixed air outlet pressure                         
        FLOW            29 - Extract air mass flow rate                        
        CONTROL         38 - Outside air damper position (0=closed, 1=open)    
        CONTROL         39 - Recirc air damper position (0=open if PAR(16)=0)  
        CONTROL         40 - Extract air damper position (0=closed, 1=open)    
        CONTROL         37 - Minimum outside air damper position (0=closed,1=op

 2     OUTPUTS:
        TEMPERATURE      0 - Mixed air dry bulb temperature                    
        HUMIDITY         0 - Mixed air humidity ratio                          
        FLOW             2 - Mixed air mass flow rate                          
        PRESSURE        28 - Extract air gauge pressure                        
        FLOW             1 - Total outside dry air mass flow rate              
        FLOW            30 - Recirc air mass flow rate                         
        FLOW             0 - Exhaust air mass flow rate                        
        FLOW             0 - Mass flow rate through minimum outside air damper 

 3     PARAMETERS:
           0.00000     Outside air damper: opposed (0) or parallel (1) (-)    
           0.00000     Recirc air damper: opposed (0) or parallel (1) (-)     
           0.00000     Exhaust air damper: opposed (0) or parallel (1) (-)    
           0.00000     Minimum outside air damper: opposed (0) or parallel (1)
          0.138000E-03 Open resist. for outside air damper (0.001/k.m)        
          0.239000E-03 Open resist. for recirc air damper (0.001/k.m)         
          0.239000E-03 Open resist. for exhaust air damper (0.001/k.m)        
          0.178000E-02 Open resist. for minimum outside air damper (0.001/k.m)
           1.32000     Face area of outside air damper (m2)                   
           1.05000     Face area of recirc air damper (m2)                    
           1.05000     Face area of exhaust air damper (m2)                   
          0.380000     Face area of minimum outside air damper (m2)           
          0.100000E-01 Leakage for outside air damper (fraction of full flow) 
          0.100000E-01 Leakage for recirc air damper (fraction of full flow) (
          0.100000E-01 Leakage for exhaust air damper (fraction of full flow) 
          0.100000E-01 Leakage for minimum outside air damper (fraction of ful
          0.467000E-03 Fixed resistance in outside air branch (0.001/k.m)     
          0.665000E-03 Fixed resistance in recirc air branch (0.001/k.m)      
          0.164000E-03 Fixed resistance in exhaust air branch (0.001/k.m)     
           1.00000     0=invert return air damper, 1=not inverted (-)         

 UNIT  31      TYPE 341
 Fluid resistance                                                        

 1     INPUTS:
        FLOW             2 - Mass flow rate                                    
        PRESSURE         3 - Outlet pressure                                   

 2     OUTPUTS:
        PRESSURE         2 - Inlet pressure                                    

 3     PARAMETERS:
          0.546000E-03 flow resistance  (0.001/kg.m)                          

 UNIT  32      TYPE 350
 Fan or pump                                                             

 1     INPUTS:
        FLOW             2 - mass flow rate of fluid                           
        PRESSURE         4 - outlet pressure                                   
        OTHER            1 - fan or pump rotational speed                      

 2     OUTPUTS:
        PRESSURE         3 - inlet pressure                                    
        POWER            1 - fluid stream heat addition rate                   
        POWER            0 - power consumption                                 

 3     PARAMETERS:
           4.29040     1st pressure coefficient                               
          -1.38700     2nd pressure coefficient                               
           4.22930     3rd pressure coefficient                               
          -3.92920     4th pressure coefficient                               
          0.853400     5th pressure coefficient                               
          0.116200     1st efficiency coefficient                             
           1.54040     2nd efficiency coefficient                             
          -1.48250     3rd efficiency coefficient                             
          0.766400     4th efficiency coefficient                             
         -0.197100     5th efficiency coefficient                             
          0.685800     diameter (m)                                           
           1.00000     mode: air=1, water=2                                   
           1.00000     lowest valid normalized flow (-)                       
           2.00000     highest valid normalized flow (-)                      

 UNIT  33      TYPE 341
 Fluid resistance                                                        

 1     INPUTS:
        FLOW             2 - Mass flow rate                                    
        PRESSURE         5 - Outlet pressure                                   

 2     OUTPUTS:
        PRESSURE         4 - Inlet pressure                                    

 3     PARAMETERS:
          0.164000E-03 flow resistance  (0.001/kg.m)                          

 UNIT  34      TYPE 346
 Asymmetric flow split                                                   

 1     INPUTS:
        FLOW             2 - Inlet flow rate                                   
        PRESSURE         6 - Pressure at main outlet                           
        FLOW             3 - Mass flow rate through branch outlet              

 2     OUTPUTS:
        PRESSURE         5 - Inlet pressure                                    
        FLOW             4 - Mass flow rate through main outlet                
        PRESSURE         7 - Pressure at branch outlet                         

 3     PARAMETERS:
          0.176000E-03 Inlet resistance  (0.001/k.m)                          
          0.844000E-03 Resistance of main outlet  (0.001/k.m)                 
          0.662000E-04 Resistance of branch outlet (0.001/k.m)                

 UNIT  35      TYPE 346
 Asymmetric flow split                                                   

 1     INPUTS:
        FLOW             4 - Inlet flow rate                                   
        PRESSURE         8 - Pressure at main outlet                           
        FLOW             5 - Mass flow rate through branch outlet              

 2     OUTPUTS:
        PRESSURE         6 - Inlet pressure                                    
        FLOW             6 - Mass flow rate through main outlet                
        PRESSURE         9 - Pressure at branch outlet                         

 3     PARAMETERS:
          0.371000E-04 Inlet resistance  (0.001/k.m)                          
          0.259000E-02 Resistance of main outlet  (0.001/k.m)                 
          0.131000E-02 Resistance of branch outlet (0.001/k.m)                

 UNIT  36      TYPE 346
 Asymmetric flow split                                                   

 1     INPUTS:
        FLOW             6 - Inlet flow rate                                   
        PRESSURE        10 - Pressure at main outlet                           
        FLOW             7 - Mass flow rate through branch outlet              

 2     OUTPUTS:
        PRESSURE         8 - Inlet pressure                                    
        FLOW             8 - Mass flow rate through main outlet                
        PRESSURE        11 - Pressure at branch outlet                         

 3     PARAMETERS:
          0.211000E-03 Inlet resistance  (0.001/k.m)                          
          0.128000E-01 Resistance of main outlet  (0.001/k.m)                 
          0.223000E-02 Resistance of branch outlet (0.001/k.m)                

 UNIT  37      TYPE 346
 Asymmetric flow split                                                   

 1     INPUTS:
        FLOW             8 - Inlet flow rate                                   
        PRESSURE        12 - Pressure at main outlet                           
        FLOW             9 - Mass flow rate through branch outlet              

 2     OUTPUTS:
        PRESSURE        10 - Inlet pressure                                    
        FLOW            10 - Mass flow rate through main outlet                
        PRESSURE        13 - Pressure at branch outlet                         

 3     PARAMETERS:
          0.730000E-03 Inlet resistance  (0.001/k.m)                          
          0.128000E-01 Resistance of main outlet  (0.001/k.m)                 
          0.938000E-02 Resistance of branch outlet (0.001/k.m)                

 UNIT  38      TYPE 346
 Asymmetric flow split                                                   

 1     INPUTS:
        FLOW            10 - Inlet flow rate                                   
        PRESSURE        14 - Pressure at main outlet                           
        FLOW            11 - Mass flow rate through branch outlet              

 2     OUTPUTS:
        PRESSURE        12 - Inlet pressure                                    
        FLOW            12 - Mass flow rate through main outlet                
        PRESSURE        15 - Pressure at branch outlet                         

 3     PARAMETERS:
          0.731000E-02 Inlet resistance  (0.001/k.m)                          
          0.895000E-01 Resistance of main outlet  (0.001/k.m)                 
          0.942000E-01 Resistance of branch outlet (0.001/k.m)                

 UNIT  39      TYPE 526
 Motorized pressure-independent VAV box                                  

 1     INPUTS:
        PRESSURE         7 - inlet pressure                                    
        PRESSURE        16 - outlet pressure                                   
        CONTROL         48 - demanded flowrate (normalized to nominal)         
        FLOW             3 - air mass flow rate                                

 2     OUTPUTS:
        FLOW             3 - air mass flow rate                                
        CONTROL         77 - damper position (0=closed, 1=open)                
        CONTROL          0 - fractional motor velocity                         
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by valve/damper          

 3     PARAMETERS:
           4.33000     nominal volumetric flow rate (m3/s)                    
          0.490000     face area of damper(s) (m2)                            
          0.999000E-01 additional pressure drop at nominal flow (kPa)         
           100.000     actuator travel time (0-90 deg) (s)                    
           0.00000     minimum fractional motor speed (-)                     
           0.00000     hysteresis (-)                                         
           9.99000     controller gain (frac speed/frac error)                

 UNIT  40      TYPE 526
 Motorized pressure-independent VAV box                                  

 1     INPUTS:
        PRESSURE         9 - inlet pressure                                    
        PRESSURE        17 - outlet pressure                                   
        CONTROL         49 - demanded flowrate (normalized to nominal)         
        FLOW             5 - air mass flow rate                                

 2     OUTPUTS:
        FLOW             5 - air mass flow rate                                
        CONTROL         78 - damper position (0=closed, 1=open)                
        CONTROL          0 - fractional motor velocity                         
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by valve/damper          

 3     PARAMETERS:
           2.36900     nominal volumetric flow rate (m3/s)                    
          0.245000     face area of damper(s) (m2)                            
          0.999000E-01 additional pressure drop at nominal flow (kPa)         
           100.000     actuator travel time (0-90 deg) (s)                    
           0.00000     minimum fractional motor speed (-)                     
           0.00000     hysteresis (-)                                         
           9.99000     controller gain (frac speed/frac error)                

 UNIT  41      TYPE 526
 Motorized pressure-independent VAV box                                  

 1     INPUTS:
        PRESSURE        11 - inlet pressure                                    
        PRESSURE        18 - outlet pressure                                   
        CONTROL         50 - demanded flowrate (normalized to nominal)         
        FLOW             7 - air mass flow rate                                

 2     OUTPUTS:
        FLOW             7 - air mass flow rate                                
        CONTROL         79 - damper position (0=closed, 1=open)                
        CONTROL          0 - fractional motor velocity                         
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by valve/damper          

 3     PARAMETERS:
          0.837000     nominal volumetric flow rate (m3/s)                    
          0.128000     face area of damper(s) (m2)                            
          0.999000E-01 additional pressure drop at nominal flow (kPa)         
           100.000     actuator travel time (0-90 deg) (s)                    
           0.00000     minimum fractional motor speed (-)                     
           0.00000     hysteresis (-)                                         
           9.90000     controller gain (frac speed/frac error)                

 UNIT  42      TYPE 526
 Motorized pressure-independent VAV box                                  

 1     INPUTS:
        PRESSURE        13 - inlet pressure                                    
        PRESSURE        19 - outlet pressure                                   
        CONTROL         51 - demanded flowrate (normalized to nominal)         
        FLOW             9 - air mass flow rate                                

 2     OUTPUTS:
        FLOW             9 - air mass flow rate                                
        CONTROL         80 - damper position (0=closed, 1=open)                
        CONTROL          0 - fractional motor velocity                         
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by valve/damper          

 3     PARAMETERS:
          0.801000     nominal volumetric flow rate (m3/s)                    
          0.128000     face area of damper(s) (m2)                            
          0.999000E-01 additional pressure drop at nominal flow (kPa)         
           100.000     actuator travel time (0-90 deg) (s)                    
           0.00000     minimum fractional motor speed (-)                     
           0.00000     hysteresis (-)                                         
           9.99000     controller gain (frac speed/frac error)                

 UNIT  43      TYPE 526
 Motorized pressure-independent VAV box                                  

 1     INPUTS:
        PRESSURE        15 - inlet pressure                                    
        PRESSURE        20 - outlet pressure                                   
        CONTROL         52 - demanded flowrate (normalized to nominal)         
        FLOW            11 - air mass flow rate                                

 2     OUTPUTS:
        FLOW            11 - air mass flow rate                                
        CONTROL         81 - damper position (0=closed, 1=open)                
        CONTROL          0 - fractional motor velocity                         
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by valve/damper          

 3     PARAMETERS:
          0.302000     nominal volumetric flow rate (m3/s)                    
          0.494000E-01 face area of damper(s) (m2)                            
          0.990000E-01 additional pressure drop at nominal flow (kPa)         
           100.000     actuator travel time (0-90 deg) (s)                    
           0.00000     minimum fractional motor speed (-)                     
           0.00000     hysteresis (-)                                         
           9.99000     controller gain (frac speed/frac error)                

 UNIT  44      TYPE 525
 Motorized pressure-independent VAV box                                  

 1     INPUTS:
        FLOW            12 - air mass flow rate                                
        PRESSURE        21 - outlet pressure                                   
        CONTROL         53 - demanded flowrate (normalized to nominal)         

 2     OUTPUTS:
        PRESSURE        14 - inlet pressure                                    
        CONTROL         82 - damper position (0=closed, 1=open)                
        CONTROL          0 - fractional motor velocity                         
        CONTROL          0 - number of stops/starts/reversals                  
        CONTROL          0 - total distance travelled by valve/damper          

 3     PARAMETERS:
          0.132000     nominal volumetric flow rate (m3/s)                    
          0.240000E-01 face area of damper(s) (m2)                            
          0.990000E-01 additional pressure drop at nominal flow (kPa)         
           100.000     actuator travel time (0-90 deg) (s)                    
           0.00000     minimum fractional motor speed (-)                     
           0.00000     hysteresis (-)                                         
           9.99000     controller gain (frac speed/frac error)                

 UNIT  45      TYPE 349
 Room air mass balance                                                   

 1     INPUTS:
        FLOW             3 - supply air mass flow rate (positive in)           
        PRESSURE        21 - pressure of 1st adjacent zone                     
        FLOW            13 - mass flow rate to 2nd adjacent zone (positive out)
        PRESSURE        16 - room pressure                                     
        PRESSURE        30 - ambient pressure                                  

 2     OUTPUTS:
        FLOW            19 - return air mass flow rate (positive out)          
        FLOW            18 - mass flow rate from 1st adjacent zone (positive in
        FLOW            31 - leakage mass flow rate to ambient (positive out)  

 3     PARAMETERS:
          0.100000     resistance to 1st adjacent zone [0.001/(kg m)]         
           1.00000     leakage resistance [0.001/(kg m)]                      
           0.00000     local extract fan mass flow rate [kg/s]                

 UNIT  46      TYPE 349
 Room air mass balance                                                   

 1     INPUTS:
        FLOW             5 - supply air mass flow rate (positive in)           
        PRESSURE        16 - pressure of 1st adjacent zone                     
        FLOW            14 - mass flow rate to 2nd adjacent zone (positive out)
        PRESSURE        17 - room pressure                                     
        PRESSURE        30 - ambient pressure                                  

 2     OUTPUTS:
        FLOW            20 - return air mass flow rate (positive out)          
        FLOW            13 - mass flow rate from 1st adjacent zone (positive in
        FLOW            32 - leakage mass flow rate to ambient (positive out)  

 3     PARAMETERS:
          0.100000     resistance to 1st adjacent zone [0.001/(kg m)]         
           1.00000     leakage resistance [0.001/(kg m)]                      
           0.00000     local extract fan mass flow rate [kg/s]                

 UNIT  47      TYPE 349
 Room air mass balance                                                   

 1     INPUTS:
        FLOW             7 - supply air mass flow rate (positive in)           
        PRESSURE        17 - pressure of 1st adjacent zone                     
        FLOW            15 - mass flow rate to 2nd adjacent zone (positive out)
        PRESSURE        18 - room pressure                                     
        PRESSURE        30 - ambient pressure                                  

 2     OUTPUTS:
        FLOW            21 - return air mass flow rate (positive out)          
        FLOW            14 - mass flow rate from 1st adjacent zone (positive in
        FLOW            33 - leakage mass flow rate to ambient (positive out)  

 3     PARAMETERS:
          0.100000     resistance to 1st adjacent zone [0.001/(kg m)]         
           1.00000     leakage resistance [0.001/(kg m)]                      
           0.00000     local extract fan mass flow rate [kg/s]                

 UNIT  48      TYPE 349
 Room air mass balance                                                   

 1     INPUTS:
        FLOW             9 - supply air mass flow rate (positive in)           
        PRESSURE        18 - pressure of 1st adjacent zone                     
        FLOW            16 - mass flow rate to 2nd adjacent zone (positive out)
        PRESSURE        19 - room pressure                                     
        PRESSURE        30 - ambient pressure                                  

 2     OUTPUTS:
        FLOW            22 - return air mass flow rate (positive out)          
        FLOW            15 - mass flow rate from 1st adjacent zone (positive in
        FLOW            34 - leakage mass flow rate to ambient (positive out)  

 3     PARAMETERS:
          0.100000     resistance to 1st adjacent zone [0.001/(kg m)]         
           1.00000     leakage resistance [0.001/(kg m)]                      
           0.00000     local extract fan mass flow rate [kg/s]                

 UNIT  49      TYPE 349
 Room air mass balance                                                   

 1     INPUTS:
        FLOW            11 - supply air mass flow rate (positive in)           
        PRESSURE        19 - pressure of 1st adjacent zone                     
        FLOW            17 - mass flow rate to 2nd adjacent zone (positive out)
        PRESSURE        20 - room pressure                                     
        PRESSURE        30 - ambient pressure                                  

 2     OUTPUTS:
        FLOW            23 - return air mass flow rate (positive out)          
        FLOW            16 - mass flow rate from 1st adjacent zone (positive in
        FLOW            35 - leakage mass flow rate to ambient (positive out)  

 3     PARAMETERS:
          0.100000     resistance to 1st adjacent zone [0.001/(kg m)]         
           1.00000     leakage resistance [0.001/(kg m)]                      
           0.00000     local extract fan mass flow rate [kg/s]                

 UNIT  50      TYPE 349
 Room air mass balance                                                   

 1     INPUTS:
        FLOW            12 - supply air mass flow rate (positive in)           
        PRESSURE        20 - pressure of 1st adjacent zone                     
        FLOW            18 - mass flow rate to 2nd adjacent zone (positive out)
        PRESSURE        21 - room pressure                                     
        PRESSURE        30 - ambient pressure                                  

 2     OUTPUTS:
        FLOW            24 - return air mass flow rate (positive out)          
        FLOW            17 - mass flow rate from 1st adjacent zone (positive in
        FLOW            36 - leakage mass flow rate to ambient (positive out)  

 3     PARAMETERS:
          0.100000     resistance to 1st adjacent zone [0.001/(kg m)]         
           1.00000     leakage resistance [0.001/(kg m)]                      
           0.00000     local extract fan mass flow rate [kg/s]                

 UNIT  51      TYPE 348
 Flow merge                                                              

 1     INPUTS:
        FLOW            22 - Inlet flow rate 1                                 
        FLOW            24 - Inlet flow rate 2                                 
        PRESSURE        22 - Pressure at outlet                                

 2     OUTPUTS:
        FLOW            25 - Mass flow rate at outlet                          
        PRESSURE        19 - Inlet pressure 1                                  
        PRESSURE        21 - Inlet pressure 2                                  

 3     PARAMETERS:
          0.847600E-01 Inlet resistance 1 (0.001/k.m)                         
           1.89750     Inlet resistance 2 (0.001/k.m)                         
          0.150000E-02 Resistance of outlet (0.001/k.m)                       

 UNIT  52      TYPE 348
 Flow merge                                                              

 1     INPUTS:
        FLOW            23 - Inlet flow rate 1                                 
        FLOW            25 - Inlet flow rate 2                                 
        PRESSURE        23 - Pressure at outlet                                

 2     OUTPUTS:
        FLOW            26 - Mass flow rate at outlet                          
        PRESSURE        20 - Inlet pressure 1                                  
        PRESSURE        22 - Inlet pressure 2                                  

 3     PARAMETERS:
          0.353960     Inlet resistance 1 (0.001/k.m)                         
          0.494000E-03 Inlet resistance 2 (0.001/k.m)                         
          0.922000E-03 Resistance of outlet (0.001/k.m)                       

 UNIT  53      TYPE 348
 Flow merge                                                              

 1     INPUTS:
        FLOW            21 - Inlet flow rate 1                                 
        FLOW            26 - Inlet flow rate 2                                 
        PRESSURE        24 - Pressure at outlet                                

 2     OUTPUTS:
        FLOW            27 - Mass flow rate at outlet                          
        PRESSURE        18 - Inlet pressure 1                                  
        PRESSURE        23 - Inlet pressure 2                                  

 3     PARAMETERS:
          0.566000E-01 Inlet resistance 1 (0.001/k.m)                         
          0.541000E-02 Inlet resistance 2 (0.001/k.m)                         
          0.749000E-04 Resistance of outlet (0.001/k.m)                       

 UNIT  54      TYPE 348
 Flow merge                                                              

 1     INPUTS:
        FLOW            20 - Inlet flow rate 1                                 
        FLOW            27 - Inlet flow rate 2                                 
        PRESSURE        25 - Pressure at outlet                                

 2     OUTPUTS:
        FLOW            28 - Mass flow rate at outlet                          
        PRESSURE        17 - Inlet pressure 1                                  
        PRESSURE        24 - Inlet pressure 2                                  

 3     PARAMETERS:
          0.653000E-02 Inlet resistance 1 (0.001/k.m)                         
          0.271000E-03 Inlet resistance 2 (0.001/k.m)                         
          0.402000E-04 Resistance of outlet (0.001/k.m)                       

 UNIT  55      TYPE 348
 Flow merge                                                              

 1     INPUTS:
        FLOW            19 - Inlet flow rate 1                                 
        FLOW            28 - Inlet flow rate 2                                 
        PRESSURE        26 - Pressure at outlet                                

 2     OUTPUTS:
        FLOW            29 - Mass flow rate at outlet                          
        PRESSURE        16 - Inlet pressure 1                                  
        PRESSURE        25 - Inlet pressure 2                                  

 3     PARAMETERS:
          0.263200E-02 Inlet resistance 1 (0.001/k.m)                         
          0.999990E-03 Inlet resistance 2 (0.001/k.m)                         
          0.649000E-03 Resistance of outlet (0.001/k.m)                       

 UNIT  56      TYPE 350
 Fan or pump                                                             

 1     INPUTS:
        FLOW            29 - mass flow rate of fluid                           
        PRESSURE        27 - outlet pressure                                   
        OTHER            2 - fan or pump rotational speed                      

 2     OUTPUTS:
        PRESSURE        26 - inlet pressure                                    
        POWER            2 - fluid stream heat addition rate                   
        POWER            0 - power consumption                                 

 3     PARAMETERS:
           4.19370     1st pressure coefficient                               
          -1.63370     2nd pressure coefficient                               
           12.2110     3rd pressure coefficient                               
          -23.9619     4th pressure coefficient                               
           9.81620     5th pressure coefficient                               
          0.619000E-01 1st efficiency coefficient                             
           3.14170     2nd efficiency coefficient                             
          -5.75510     3rd efficiency coefficient                             
           6.16760     4th efficiency coefficient                             
          -3.37480     5th efficiency coefficient                             
           1.13000     diameter (m)                                           
           1.00000     mode: air=1, water=2                                   
          0.700000     lowest valid normalized flow (-)                       
           1.00000     highest valid normalized flow (-)                      

 UNIT  57      TYPE 341
 Fluid resistance                                                        

 1     INPUTS:
        FLOW            29 - Mass flow rate                                    
        PRESSURE        28 - Outlet pressure                                   

 2     OUTPUTS:
        PRESSURE        27 - Inlet pressure                                    

 3     PARAMETERS:
          0.118000E-03 flow resistance  (0.001/kg.m)                          

 UNIT  58      TYPE 367
 Mixing of two moist air streams                                         

 1     INPUTS:
        TEMPERATURE      1 - Stream 1 dry bulb temperature                     
        HUMIDITY         1 - Stream 1 humidity ratio                           
        FLOW             1 - Stream 1 mass flow rate                           
        TEMPERATURE     54 - Stream 2 dry bulb temperature                     
        HUMIDITY        16 - Stream 2 humidity ratio                           
        FLOW            30 - Stream 2 mass flow rate                           

 2     OUTPUTS:
        TEMPERATURE      2 - Mixed air dry bulb temperature                    
        HUMIDITY         2 - Mixed air humidity ratio                          
        FLOW             0 - Mixed air mass flow rate                          

 3     PARAMETERS:
           0.00000     (dummy)                                                

 UNIT  59      TYPE 524
 Coil + three port valve, calculates flow                                

 1     INPUTS:
        TEMPERATURE      2 - Inlet air dry bulb temperature                    
        HUMIDITY         2 - Inlet air humidity ratio                          
        PRESSURE         1 - Outlet air pressure                               
        FLOW             2 - Dry air mass flow rate                            
        TEMPERATURE     55 - Inlet water temperature                           
        PRESSURE        32 - Inlet water pressure                              
        PRESSURE        33 - Outlet water pressure                             
        CONTROL         41 - Valve stem position                               
        TEMPERATURE     57 - Effective coil surface temperature (same as 1st o/

 2     OUTPUTS:
        TEMPERATURE     57 - Effective coil surface temperature                
        TEMPERATURE      3 - Outlet dry bulb air temperature                   
        HUMIDITY         3 - Outlet air humidity ratio                         
        PRESSURE         0 - Inlet air pressure                                
        TEMPERATURE     56 - Outlet water temperature                          
        FLOW             0 - Primary circuit water mass flow rate              
        FLOW            40 - Water mass flow rate through coil                 
        TEMPERATURE      0 - Mixed return water temperature                    
        POWER            3 - Total heat transfer to the air                    
        CONTROL          0 - Sensible heat ratio                               
        CONTROL          0 - Coil effectiveness                                
        CONTROL          0 - Coil by-pass factor                               
        ENERGY           0 - Outlet air specific enthalpy                      
        CONTROL          0 - Outlet air relative humidity                      
        TEMPERATURE      0 - Outlet air wet-bulb temperature                   

 3     PARAMETERS:
           1.00000     Method : 0 = steady state, 1 = dynamic                 
           0.00000     Fault  : 0 for no faults, 1 = parallel flow (cooling co
           0.00000     Psycho : 0 = no psychrometric output calcs, 1 = calcs  
           4.00000     Number of rows of tubes                                
           36.0000     Number of tubes per row                                
           36.0000     Number of parallel water circuits                      
          0.241000     Length of finned section in direction of flow (m)      
           1.37000     Height of finned section (m)                           
           2.77000     Width of finned section (m)                            
          0.159000E-01 Tube outside diameter (m)                              
          0.787400E-03 Tube wall thickness (m)                                
           2.00000     Tube material (Al=1,Cu=2,Fe=3,CaCO3=4)                 
          0.212000E-02 Fin spacing (pitch) (m)                                
          0.216000E-03 Fin thickness (m)                                      
           1.00000     Fin material (Al=1,Cu=2,Fe=3)                          
          0.107000E-02 Flow resistance on air side (0.001 kg.m)               
           1.20100     Coil water flow resistance (0.001 kg.m)                
          0.100000E+07 By-pass water flow resistance (0.001 kg.m)             
           1.00000     Valve type: 0=lin/lin, 1=eq%(flow)/lin(byp), 2=lin/eq% 
           32.6800     Valve capacity (Kv) (m3/hr @ 1 bar)                    
           3.54000     Valve curvature parameter (0=linear) (-)               
           35.0000     Valve rangability (-)                                  
          0.100000E-03 Valve leakage (fractional flow) (-)                    

 UNIT  60      TYPE 366
 Ideal heating of fluid stream                                           

 1     INPUTS:
        FLOW             2 - mass flow rate                                    
        TEMPERATURE      3 - inlet temperature                                 
        POWER            1 - rate of heat addition                             

 2     OUTPUTS:
        TEMPERATURE      4 - outlet temperature                                

 3     PARAMETERS:
           1.00000     fluid: 1 = air, any other value + water (-)            
           30.0000     time constant (s)                                      

 UNIT  61      TYPE 524
 Coil + three port valve, calculates flow                                

 1     INPUTS:
        TEMPERATURE      4 - Inlet air dry bulb temperature                    
        HUMIDITY         3 - Inlet air humidity ratio                          
        PRESSURE         1 - Outlet air pressure                               
        FLOW             3 - Dry air mass flow rate                            
        TEMPERATURE     58 - Inlet water temperature                           
        PRESSURE        34 - Inlet water pressure                              
        PRESSURE        35 - Outlet water pressure                             
        CONTROL         42 - Valve stem position                               
        TEMPERATURE     70 - Effective coil surface temperature (same as 1st o/

 2     OUTPUTS:
        TEMPERATURE     70 - Effective coil surface temperature                
        TEMPERATURE      5 - Outlet dry bulb air temperature                   
        HUMIDITY         4 - Outlet air humidity ratio                         
        PRESSURE         0 - Inlet air pressure                                
        TEMPERATURE     64 - Outlet water temperature                          
        FLOW             0 - Primary circuit water mass flow rate              
        FLOW            41 - Water mass flow rate through coil                 
        TEMPERATURE      0 - Mixed return water temperature                    
        POWER            4 - Total heat transfer to the air                    
        CONTROL          0 - Sensible heat ratio                               
        CONTROL          0 - Coil effectiveness                                
        CONTROL          0 - Coil by-pass factor                               
        ENERGY           0 - Outlet air specific enthalpy                      
        CONTROL          0 - Outlet air relative humidity                      
        TEMPERATURE      0 - Outlet air wet-bulb temperature                   

 3     PARAMETERS:
           1.00000     Method : 0 = steady state, 1 = dynamic                 
           0.00000     Fault  : 0 for no faults, 1 = parallel flow (cooling co
           0.00000     Psycho : 0 = no psychrometric output calcs, 1 = calcs  
           1.00000     Number of rows of tubes                                
           28.0000     Number of tubes per row                                
           2.00000     Number of parallel water circuits                      
          0.275000E-01 Length of finned section in direction of flow (m)      
          0.914000     Height of finned section (m)                           
          0.710000     Width of finned section (m)                            
          0.127000E-01 Tube outside diameter (m)                              
          0.406000E-03 Tube wall thickness (m)                                
           2.00000     Tube material (Al=1,Cu=2,Fe=3,CaCO3=4)                 
          0.254000E-02 Fin spacing (pitch) (m)                                
          0.152000E-03 Fin thickness (m)                                      
           1.00000     Fin material (Al=1,Cu=2,Fe=3)                          
          0.230000E-02 Flow resistance on air side (0.001 kg.m)               
           1.26000     Coil water flow resistance (0.001 kg.m)                
          0.100000E+07 By-pass water flow resistance (0.001 kg.m)             
           1.00000     Valve type: 0=lin/lin, 1=eq%(flow)/lin(byp), 2=lin/eq% 
           2.51000     Valve capacity (Kv) (m3/hr @ 1 bar)                    
           3.22000     Valve curvature parameter (0=linear) (-)               
           50.0000     Valve rangability (-)                                  
          0.200000E-03 Valve leakage (fractional flow) (-)                    

 UNIT  62      TYPE 524
 Coil + three port valve, calculates flow                                

 1     INPUTS:
        TEMPERATURE      4 - Inlet air dry bulb temperature                    
        HUMIDITY         3 - Inlet air humidity ratio                          
        PRESSURE         1 - Outlet air pressure                               
        FLOW             5 - Dry air mass flow rate                            
        TEMPERATURE     59 - Inlet water temperature                           
        PRESSURE        36 - Inlet water pressure                              
        PRESSURE        37 - Outlet water pressure                             
        CONTROL         43 - Valve stem position                               
        TEMPERATURE     71 - Effective coil surface temperature (same as 1st o/

 2     OUTPUTS:
        TEMPERATURE     71 - Effective coil surface temperature                
        TEMPERATURE      6 - Outlet dry bulb air temperature                   
        HUMIDITY         5 - Outlet air humidity ratio                         
        PRESSURE         0 - Inlet air pressure                                
        TEMPERATURE     65 - Outlet water temperature                          
        FLOW             0 - Primary circuit water mass flow rate              
        FLOW            42 - Water mass flow rate through coil                 
        TEMPERATURE      0 - Mixed return water temperature                    
        POWER            5 - Total heat transfer to the air                    
        CONTROL          0 - Sensible heat ratio                               
        CONTROL          0 - Coil effectiveness                                
        CONTROL          0 - Coil by-pass factor                               
        ENERGY           0 - Outlet air specific enthalpy                      
        CONTROL          0 - Outlet air relative humidity                      
        TEMPERATURE      0 - Outlet air wet-bulb temperature                   

 3     PARAMETERS:
           1.00000     Method : 0 = steady state, 1 = dynamic                 
           0.00000     Fault  : 0 for no faults, 1 = parallel flow (cooling co
           0.00000     Psycho : 0 = no psychrometric output calcs, 1 = calcs  
           1.00000     Number of rows of tubes                                
           14.0000     Number of tubes per row                                
           1.00000     Number of parallel water circuits                      
          0.275000E-01 Length of finned section in direction of flow (m)      
          0.457000     Height of finned section (m)                           
          0.711000     Width of finned section (m)                            
          0.127000E-01 Tube outside diameter (m)                              
          0.406000E-03 Tube wall thickness (m)                                
           2.00000     Tube material (Al=1,Cu=2,Fe=3,CaCO3=4)                 
          0.254000E-02 Fin spacing (pitch) (m)                                
          0.152000E-03 Fin thickness (m)                                      
           1.00000     Fin material (Al=1,Cu=2,Fe=3)                          
          0.910000E-02 Flow resistance on air side (0.001 kg.m)               
           5.04000     Coil water flow resistance (0.001 kg.m)                
          0.100000E+07 By-pass water flow resistance (0.001 kg.m)             
           1.00000     Valve type: 0=lin/lin, 1=eq%(flow)/lin(byp), 2=lin/eq% 
           1.61000     Valve capacity (Kv) (m3/hr @ 1 bar)                    
           3.22000     Valve curvature parameter (0=linear) (-)               
           50.0000     Valve rangability (-)                                  
          0.200000E-03 Valve leakage (fractional flow) (-)                    

 UNIT  63      TYPE 524
 Coil + three port valve, calculates flow                                

 1     INPUTS:
        TEMPERATURE      4 - Inlet air dry bulb temperature                    
        HUMIDITY         3 - Inlet air humidity ratio                          
        PRESSURE         1 - Outlet air pressure                               
        FLOW             7 - Dry air mass flow rate                            
        TEMPERATURE     60 - Inlet water temperature                           
        PRESSURE        38 - Inlet water pressure                              
        PRESSURE        39 - Outlet water pressure                             
        CONTROL         44 - Valve stem position                               
        TEMPERATURE     72 - Effective coil surface temperature (same as 1st o/

 2     OUTPUTS:
        TEMPERATURE     72 - Effective coil surface temperature                
        TEMPERATURE      7 - Outlet dry bulb air temperature                   
        HUMIDITY         6 - Outlet air humidity ratio                         
        PRESSURE         0 - Inlet air pressure                                
        TEMPERATURE     66 - Outlet water temperature                          
        FLOW             0 - Primary circuit water mass flow rate              
        FLOW            43 - Water mass flow rate through coil                 
        TEMPERATURE      0 - Mixed return water temperature                    
        POWER            6 - Total heat transfer to the air                    
        CONTROL          0 - Sensible heat ratio                               
        CONTROL          0 - Coil effectiveness                                
        CONTROL          0 - Coil by-pass factor                               
        ENERGY           0 - Outlet air specific enthalpy                      
        CONTROL          0 - Outlet air relative humidity                      
        TEMPERATURE      0 - Outlet air wet-bulb temperature                   

 3     PARAMETERS:
           1.00000     Method : 0 = steady state, 1 = dynamic                 
           0.00000     Fault  : 0 for no faults, 1 = parallel flow (cooling co
           0.00000     Psycho : 0 = no psychrometric output calcs, 1 = calcs  
           1.00000     Number of rows of tubes                                
           14.0000     Number of tubes per row                                
           1.00000     Number of parallel water circuits                      
          0.275000E-01 Length of finned section in direction of flow (m)      
          0.457000     Height of finned section (m)                           
          0.610000     Width of finned section (m)                            
          0.127000E-01 Tube outside diameter (m)                              
          0.406000E-03 Tube wall thickness (m)                                
           2.00000     Tube material (Al=1,Cu=2,Fe=3,CaCO3=4)                 
          0.254000E-02 Fin spacing (pitch) (m)                                
          0.152000E-03 Fin thickness (m)                                      
           1.00000     Fin material (Al=1,Cu=2,Fe=3)                          
          0.260000E-01 Flow resistance on air side (0.001 kg.m)               
           4.53000     Coil water flow resistance (0.001 kg.m)                
          0.100000E+07 By-pass water flow resistance (0.001 kg.m)             
           1.00000     Valve type: 0=lin/lin, 1=eq%(flow)/lin(byp), 2=lin/eq% 
          0.640000     Valve capacity (Kv) (m3/hr @ 1 bar)                    
           3.22000     Valve curvature parameter (0=linear) (-)               
           50.0000     Valve rangability (-)                                  
          0.200000E-03 Valve leakage (fractional flow) (-)                    

 UNIT  64      TYPE 524
 Coil + three port valve, calculates flow                                

 1     INPUTS:
        TEMPERATURE      4 - Inlet air dry bulb temperature                    
        HUMIDITY         3 - Inlet air humidity ratio                          
        PRESSURE         1 - Outlet air pressure                               
        FLOW             9 - Dry air mass flow rate                            
        TEMPERATURE     61 - Inlet water temperature                           
        PRESSURE        40 - Inlet water pressure                              
        PRESSURE        41 - Outlet water pressure                             
        CONTROL         45 - Valve stem position                               
        TEMPERATURE     73 - Effective coil surface temperature (same as 1st o/

 2     OUTPUTS:
        TEMPERATURE     73 - Effective coil surface temperature                
        TEMPERATURE      8 - Outlet dry bulb air temperature                   
        HUMIDITY         7 - Outlet air humidity ratio                         
        PRESSURE         0 - Inlet air pressure                                
        TEMPERATURE     67 - Outlet water temperature                          
        FLOW             0 - Primary circuit water mass flow rate              
        FLOW            44 - Water mass flow rate through coil                 
        TEMPERATURE      0 - Mixed return water temperature                    
        POWER            7 - Total heat transfer to the air                    
        CONTROL          0 - Sensible heat ratio                               
        CONTROL          0 - Coil effectiveness                                
        CONTROL          0 - Coil by-pass factor                               
        ENERGY           0 - Outlet air specific enthalpy                      
        CONTROL          0 - Outlet air relative humidity                      
        TEMPERATURE      0 - Outlet air wet-bulb temperature                   

 3     PARAMETERS:
           1.00000     Method : 0 = steady state, 1 = dynamic                 
           0.00000     Fault  : 0 for no faults, 1 = parallel flow (cooling co
           0.00000     Psycho : 0 = no psychrometric output calcs, 1 = calcs  
           1.00000     Number of rows of tubes                                
           14.0000     Number of tubes per row                                
           1.00000     Number of parallel water circuits                      
          0.275000E-01 Length of finned section in direction of flow (m)      
          0.457000     Height of finned section (m)                           
          0.610000     Width of finned section (m)                            
          0.127000E-01 Tube outside diameter (m)                              
          0.406000E-03 Tube wall thickness (m)                                
           2.00000     Tube material (Al=1,Cu=2,Fe=3,CaCO3=4)                 
          0.254000E-02 Fin spacing (pitch) (m)                                
          0.152000E-03 Fin thickness (m)                                      
           1.00000     Fin material (Al=1,Cu=2,Fe=3)                          
          0.260000E-01 Flow resistance on air side (0.001 kg.m)               
           4.53000     Coil water flow resistance (0.001 kg.m)                
          0.100000E+07 By-pass water flow resistance (0.001 kg.m)             
           1.00000     Valve type: 0=lin/lin, 1=eq%(flow)/lin(byp), 2=lin/eq% 
          0.640000     Valve capacity (Kv) (m3/hr @ 1 bar)                    
           3.22000     Valve curvature parameter (0=linear) (-)               
           50.0000     Valve rangability (-)                                  
          0.200000E-03 Valve leakage (fractional flow) (-)                    

 UNIT  65      TYPE 524
 Coil + three port valve, calculates flow                                

 1     INPUTS:
        TEMPERATURE      4 - Inlet air dry bulb temperature                    
        HUMIDITY         3 - Inlet air humidity ratio                          
        PRESSURE         1 - Outlet air pressure                               
        FLOW            11 - Dry air mass flow rate                            
        TEMPERATURE     62 - Inlet water temperature                           
        PRESSURE        42 - Inlet water pressure                              
        PRESSURE        43 - Outlet water pressure                             
        CONTROL         46 - Valve stem position                               
        TEMPERATURE     74 - Effective coil surface temperature (same as 1st o/

 2     OUTPUTS:
        TEMPERATURE     74 - Effective coil surface temperature                
        TEMPERATURE      9 - Outlet dry bulb air temperature                   
        HUMIDITY         8 - Outlet air humidity ratio                         
        PRESSURE         0 - Inlet air pressure                                
        TEMPERATURE     68 - Outlet water temperature                          
        FLOW             0 - Primary circuit water mass flow rate              
        FLOW            45 - Water mass flow rate through coil                 
        TEMPERATURE      0 - Mixed return water temperature                    
        POWER            8 - Total heat transfer to the air                    
        CONTROL          0 - Sensible heat ratio                               
        CONTROL          0 - Coil effectiveness                                
        CONTROL          0 - Coil by-pass factor                               
        ENERGY           0 - Outlet air specific enthalpy                      
        CONTROL          0 - Outlet air relative humidity                      
        TEMPERATURE      0 - Outlet air wet-bulb temperature                   

 3     PARAMETERS:
           1.00000     Method : 0 = steady state, 1 = dynamic                 
           0.00000     Fault  : 0 for no faults, 1 = parallel flow (cooling co
           0.00000     Psycho : 0 = no psychrometric output calcs, 1 = calcs  
           1.00000     Number of rows of tubes                                
           10.0000     Number of tubes per row                                
           2.00000     Number of parallel water circuits                      
          0.275000E-01 Length of finned section in direction of flow (m)      
          0.318000     Height of finned section (m)                           
          0.356000     Width of finned section (m)                            
          0.127000E-01 Tube outside diameter (m)                              
          0.406000E-03 Tube wall thickness (m)                                
           2.00000     Tube material (Al=1,Cu=2,Fe=3,CaCO3=4)                 
          0.254000E-02 Fin spacing (pitch) (m)                                
          0.152000E-03 Fin thickness (m)                                      
           1.00000     Fin material (Al=1,Cu=2,Fe=3)                          
          0.151000     Flow resistance on air side (0.001 kg.m)               
           8.76000     Coil water flow resistance (0.001 kg.m)                
          0.100000E+07 By-pass water flow resistance (0.001 kg.m)             
           1.00000     Valve type: 0=lin/lin, 1=eq%(flow)/lin(byp), 2=lin/eq% 
          0.400000     Valve capacity (Kv) (m3/hr @ 1 bar)                    
           3.22000     Valve curvature parameter (0=linear) (-)               
           50.0000     Valve rangability (-)                                  
          0.200000E-03 Valve leakage (fractional flow) (-)                    

 UNIT  66      TYPE 524
 Coil + three port valve, calculates flow                                

 1     INPUTS:
        TEMPERATURE      4 - Inlet air dry bulb temperature                    
        HUMIDITY         3 - Inlet air humidity ratio                          
        PRESSURE         1 - Outlet air pressure                               
        FLOW            12 - Dry air mass flow rate                            
        TEMPERATURE     63 - Inlet water temperature                           
        PRESSURE        44 - Inlet water pressure                              
        PRESSURE        45 - Outlet water pressure                             
        CONTROL         47 - Valve stem position                               
        TEMPERATURE     75 - Effective coil surface temperature (same as 1st o/

 2     OUTPUTS:
        TEMPERATURE     75 - Effective coil surface temperature                
        TEMPERATURE     10 - Outlet dry bulb air temperature                   
        HUMIDITY         9 - Outlet air humidity ratio                         
        PRESSURE         0 - Inlet air pressure                                
        TEMPERATURE     69 - Outlet water temperature                          
        FLOW             0 - Primary circuit water mass flow rate              
        FLOW            46 - Water mass flow rate through coil                 
        TEMPERATURE      0 - Mixed return water temperature                    
        POWER            9 - Total heat transfer to the air                    
        CONTROL          0 - Sensible heat ratio                               
        CONTROL          0 - Coil effectiveness                                
        CONTROL          0 - Coil by-pass factor                               
        ENERGY           0 - Outlet air specific enthalpy                      
        CONTROL          0 - Outlet air relative humidity                      
        TEMPERATURE      0 - Outlet air wet-bulb temperature                   

 3     PARAMETERS:
           1.00000     Method : 0 = steady state, 1 = dynamic                 
           0.00000     Fault  : 0 for no faults, 1 = parallel flow (cooling co
           0.00000     Psycho : 0 = no psychrometric output calcs, 1 = calcs  
           1.00000     Number of rows of tubes                                
           8.00000     Number of tubes per row                                
           1.00000     Number of parallel water circuits                      
          0.275000E-01 Length of finned section in direction of flow (m)      
          0.254000     Height of finned section (m)                           
          0.305000     Width of finned section (m)                            
          0.127000E-01 Tube outside diameter (m)                              
          0.404000E-03 Tube wall thickness (m)                                
           2.00000     Tube material (Al=1,Cu=2,Fe=3,CaCO3=4)                 
          0.254000E-02 Fin spacing (pitch) (m)                                
          0.152000E-03 Fin thickness (m)                                      
           1.00000     Fin material (Al=1,Cu=2,Fe=3)                          
          0.346000     Flow resistance on air side (0.001 kg.m)               
           50.0000     Coil water flow resistance (0.001 kg.m)                
          0.100000E+07 By-pass water flow resistance (0.001 kg.m)             
           1.00000     Valve type: 0=lin/lin, 1=eq%(flow)/lin(byp), 2=lin/eq% 
          0.250000     Valve capacity (Kv) (m3/hr @ 1 bar)                    
           3.22000     Valve curvature parameter (0=linear) (-)               
           50.0000     Valve rangability (-)                                  
          0.200000E-03 Valve leakage (fractional flow) (-)                    

 UNIT  67      TYPE 403
 Room with plenum and ducted return and interzone flows                  

 1     INPUTS:
        TEMPERATURE      5 - supply air dry bulb temperature                   
        HUMIDITY         4 - supply air humidity ratio                         
        FLOW             3 - supply dry air mass flow rate                     
        TEMPERATURE     16 - interzone 1 air dry bulb temperature              
        HUMIDITY        15 - interzone 1 air humidity ratio                    
        FLOW            18 - interzone 1 dry air mass flow rate                
        TEMPERATURE     12 - interzone 2 air dry bulb temperature              
        HUMIDITY        11 - interzone 2 air humidity ratio                    
        FLOW            13 - interzone 2 dry air mass flow rate                
        FLOW            19 - extract dry air mass flow rate                    
        TEMPERATURE      1 - ambient dry bulb temperature                      
        HUMIDITY         1 - ambient humidity ratio                            
        FLOW            31 - leakage air mass flow rate (positive out)         
        TEMPERATURE     41 - equivalent "sol-air" outdoor temperature for room 
        TEMPERATURE     47 - equivalent "sol-air" outdoor temperature for plenu
        CONTROL         83 - fractional occupancy                              
        CONTROL         89 - fractional lighting heat gain                     
        CONTROL         95 - fractional equipment heat gain                    
        POWER           10 - heat gain from supply duct                        
        POWER           11 - heat gain from extract duct                       
        TEMPERATURE     11 - room temperature                                  
        TEMPERATURE     17 - room structure temperature                        
        TEMPERATURE     23 - plenum temperature                                
        TEMPERATURE     29 - plenum structure temperature                      
        HUMIDITY        10 - room humidity ratio                               

 2     OUTPUTS:
        TEMPERATURE     11 - room temperature                                  
        TEMPERATURE     17 - room structure temperature                        
        TEMPERATURE     23 - plenum temperature                                
        TEMPERATURE     29 - plenum structure temperature                      
        HUMIDITY        10 - room humidity ratio                               
        TEMPERATURE     35 - return temperature                                
        POWER            0 - sensible heat gains of room                       
        POWER            0 - sensible heat gains of plenum                     
        FLOW             0 - water vapour gains of room                        

 3     PARAMETERS:
           1.00000     room air capacity multiplier (-)                       
           4.64000     direct resistance room air node <-> ambient (K/kW)     
          0.994000E-01 resistance room air node <-> room mass node (K/kW)     
           2.53000     resistance ambient <-> room mass node (K/kW)           
          0.100000E+12 direct resistance plenum air node <-> ambient (K/kW)   
          0.337000     resistance plenum air node <-> plenum mass node (K/kW) 
           4.13000     resistance ambient <-> plenum mass node (K/kW)         
           1.14000     resistance room air node <-> plenum air node (K/kW)    
           279000.     capacitance of room mass node (kJ/K)                   
           25800.0     capacitance of room air node (unmodified) (kJ/K)       
           125000.     capacitance of plenum mass node (kJ/K)                 
           6870.00     capacitance of plenum air node (kJ/K)                  
           1820.00     volume of room (m3)                                    
           396.000     volume of plenum (m3)                                  
           0.00000     number of occupants (-)                                
           0.00000     lighting heat gain (kW)                                
           0.00000     fraction of lighting heat gain to extract air (-)      
           0.00000     equipment heat gain (kW)                               
           3.00000     zone number (parameter file=zoneN.par, n > 0) (-)      

 UNIT  68      TYPE 403
 Room with plenum and ducted return and interzone flows                  

 1     INPUTS:
        TEMPERATURE      6 - supply air dry bulb temperature                   
        HUMIDITY         5 - supply air humidity ratio                         
        FLOW             5 - supply dry air mass flow rate                     
        TEMPERATURE     11 - interzone 1 air dry bulb temperature              
        HUMIDITY        10 - interzone 1 air humidity ratio                    
        FLOW            13 - interzone 1 dry air mass flow rate                
        TEMPERATURE     13 - interzone 2 air dry bulb temperature              
        HUMIDITY        12 - interzone 2 air humidity ratio                    
        FLOW            14 - interzone 2 dry air mass flow rate                
        FLOW            20 - extract dry air mass flow rate                    
        TEMPERATURE      1 - ambient dry bulb temperature                      
        HUMIDITY         1 - ambient humidity ratio                            
        FLOW            32 - leakage air mass flow rate (positive out)         
        TEMPERATURE     42 - equivalent "sol-air" outdoor temperature for room 
        TEMPERATURE     48 - equivalent "sol-air" outdoor temperature for plenu
        CONTROL         84 - fractional occupancy                              
        CONTROL         90 - fractional lighting heat gain                     
        CONTROL         96 - fractional equipment heat gain                    
        POWER           12 - heat gain from supply duct                        
        POWER           13 - heat gain from extract duct                       
        TEMPERATURE     12 - room temperature                                  
        TEMPERATURE     18 - room structure temperature                        
        TEMPERATURE     24 - plenum temperature                                
        TEMPERATURE     30 - plenum structure temperature                      
        HUMIDITY        11 - room humidity ratio                               

 2     OUTPUTS:
        TEMPERATURE     12 - room temperature                                  
        TEMPERATURE     18 - room structure temperature                        
        TEMPERATURE     24 - plenum temperature                                
        TEMPERATURE     30 - plenum structure temperature                      
        HUMIDITY        11 - room humidity ratio                               
        TEMPERATURE     36 - return temperature                                
        POWER            0 - sensible heat gains of room                       
        POWER            0 - sensible heat gains of plenum                     
        FLOW             0 - water vapour gains of room                        

 3     PARAMETERS:
           1.00000     room air capacity multiplier (-)                       
           6.82000     direct resistance room air node <-> ambient (K/kW)     
          0.182000     resistance room air node <-> room mass node (K/kW)     
           5.35000     resistance ambient <-> room mass node (K/kW)           
          0.100000E+12 direct resistance plenum air node <-> ambient (K/kW)   
          0.254000     resistance plenum air node <-> plenum mass node (K/kW) 
           11.4000     resistance ambient <-> plenum mass node (K/kW)         
           1.33000     resistance room air node <-> plenum air node (K/kW)    
           214000.     capacitance of room mass node (kJ/K)                   
           17800.0     capacitance of room air node (unmodified) (kJ/K)       
           152000.     capacitance of plenum mass node (kJ/K)                 
           5490.00     capacitance of plenum air node (kJ/K)                  
           1210.00     volume of room (m3)                                    
           330.000     volume of plenum (m3)                                  
           0.00000     number of occupants (-)                                
           0.00000     lighting heat gain (kW)                                
           0.00000     fraction of lighting heat gain to extract air (-)      
           0.00000     equipment heat gain (kW)                               
           5.00000     zone number (parameter file=zoneN.par, n > 0) (-)      

 UNIT  69      TYPE 403
 Room with plenum and ducted return and interzone flows                  

 1     INPUTS:
        TEMPERATURE      7 - supply air dry bulb temperature                   
        HUMIDITY         6 - supply air humidity ratio                         
        FLOW             7 - supply dry air mass flow rate                     
        TEMPERATURE     12 - interzone 1 air dry bulb temperature              
        HUMIDITY        11 - interzone 1 air humidity ratio                    
        FLOW            14 - interzone 1 dry air mass flow rate                
        TEMPERATURE     14 - interzone 2 air dry bulb temperature              
        HUMIDITY        13 - interzone 2 air humidity ratio                    
        FLOW            15 - interzone 2 dry air mass flow rate                
        FLOW            21 - extract dry air mass flow rate                    
        TEMPERATURE      1 - ambient dry bulb temperature                      
        HUMIDITY         1 - ambient humidity ratio                            
        FLOW            33 - leakage air mass flow rate (positive out)         
        TEMPERATURE     43 - equivalent "sol-air" outdoor temperature for room 
        TEMPERATURE     49 - equivalent "sol-air" outdoor temperature for plenu
        CONTROL         85 - fractional occupancy                              
        CONTROL         91 - fractional lighting heat gain                     
        CONTROL         97 - fractional equipment heat gain                    
        POWER           14 - heat gain from supply duct                        
        POWER           15 - heat gain from extract duct                       
        TEMPERATURE     13 - room temperature                                  
        TEMPERATURE     19 - room structure temperature                        
        TEMPERATURE     25 - plenum temperature                                
        TEMPERATURE     31 - plenum structure temperature                      
        HUMIDITY        12 - room humidity ratio                               

 2     OUTPUTS:
        TEMPERATURE     13 - room temperature                                  
        TEMPERATURE     19 - room structure temperature                        
        TEMPERATURE     25 - plenum temperature                                
        TEMPERATURE     31 - plenum structure temperature                      
        HUMIDITY        12 - room humidity ratio                               
        TEMPERATURE     37 - return temperature                                
        POWER            0 - sensible heat gains of room                       
        POWER            0 - sensible heat gains of plenum                     
        FLOW             0 - water vapour gains of room                        

 3     PARAMETERS:
           1.00000     room air capacity multiplier (-)                       
           32.7000     direct resistance room air node <-> ambient (K/kW)     
          0.236000     resistance room air node <-> room mass node (K/kW)     
           20.9000     resistance ambient <-> room mass node (K/kW)           
          0.100000E+12 direct resistance plenum air node <-> ambient (K/kW)   
          0.649000     resistance plenum air node <-> plenum mass node (K/kW) 
           55.8000     resistance ambient <-> plenum mass node (K/kW)         
           3.26000     resistance room air node <-> plenum air node (K/kW)    
           58500.0     capacitance of room mass node (kJ/K)                   
           9410.00     capacitance of room air node (unmodified) (kJ/K)       
           48100.0     capacitance of plenum mass node (kJ/K)                 
           2450.00     capacitance of plenum air node (kJ/K)                  
           647.000     volume of room (m3)                                    
           125.000     volume of plenum (m3)                                  
           0.00000     number of occupants (-)                                
           0.00000     lighting heat gain (kW)                                
           0.00000     fraction of lighting heat gain to extract air (-)      
           0.00000     equipment heat gain (kW)                               
           1.00000     zone number (parameter file=zoneN.par, n > 0) (-)      

 UNIT  70      TYPE 403
 Room with plenum and ducted return and interzone flows                  

 1     INPUTS:
        TEMPERATURE      8 - supply air dry bulb temperature                   
        HUMIDITY         7 - supply air humidity ratio                         
        FLOW             9 - supply dry air mass flow rate                     
        TEMPERATURE     13 - interzone 1 air dry bulb temperature              
        HUMIDITY        12 - interzone 1 air humidity ratio                    
        FLOW            15 - interzone 1 dry air mass flow rate                
        TEMPERATURE     15 - interzone 2 air dry bulb temperature              
        HUMIDITY        14 - interzone 2 air humidity ratio                    
        FLOW            16 - interzone 2 dry air mass flow rate                
        FLOW            22 - extract dry air mass flow rate                    
        TEMPERATURE      1 - ambient dry bulb temperature                      
        HUMIDITY         1 - ambient humidity ratio                            
        FLOW            34 - leakage air mass flow rate (positive out)         
        TEMPERATURE     44 - equivalent "sol-air" outdoor temperature for room 
        TEMPERATURE     50 - equivalent "sol-air" outdoor temperature for plenu
        CONTROL         86 - fractional occupancy                              
        CONTROL         92 - fractional lighting heat gain                     
        CONTROL         98 - fractional equipment heat gain                    
        POWER           16 - heat gain from supply duct                        
        POWER           17 - heat gain from extract duct                       
        TEMPERATURE     14 - room temperature                                  
        TEMPERATURE     20 - room structure temperature                        
        TEMPERATURE     26 - plenum temperature                                
        TEMPERATURE     32 - plenum structure temperature                      
        HUMIDITY        13 - room humidity ratio                               

 2     OUTPUTS:
        TEMPERATURE     14 - room temperature                                  
        TEMPERATURE     20 - room structure temperature                        
        TEMPERATURE     26 - plenum temperature                                
        TEMPERATURE     32 - plenum structure temperature                      
        HUMIDITY        13 - room humidity ratio                               
        TEMPERATURE     38 - return temperature                                
        POWER            0 - sensible heat gains of room                       
        POWER            0 - sensible heat gains of plenum                     
        FLOW             0 - water vapour gains of room                        

 3     PARAMETERS:
           1.00000     room air capacity multiplier (-)                       
           17.9000     direct resistance room air node <-> ambient (K/kW)     
          0.540000     resistance room air node <-> room mass node (K/kW)     
           8.70000     resistance ambient <-> room mass node (K/kW)           
          0.100000E+12 direct resistance plenum air node <-> ambient (K/kW)   
          0.737000     resistance plenum air node <-> plenum mass node (K/kW) 
           25.3000     resistance ambient <-> plenum mass node (K/kW)         
           3.81000     resistance room air node <-> plenum air node (K/kW)    
           76000.0     capacitance of room mass node (kJ/K)                   
           7240.00     capacitance of room air node (unmodified) (kJ/K)       
           51800.0     capacitance of plenum mass node (kJ/K)                 
           2360.00     capacitance of plenum air node (kJ/K)                  
           385.000     volume of room (m3)                                    
           107.000     volume of plenum (m3)                                  
           0.00000     number of occupants (-)                                
           0.00000     lighting heat gain (kW)                                
           0.00000     fraction of lighting heat gain to extract air (-)      
           0.00000     equipment heat gain (kW)                               
           4.00000     zone number (parameter file=zoneN.par, n > 0) (-)      

 UNIT  71      TYPE 403
 Room with plenum and ducted return and interzone flows                  

 1     INPUTS:
        TEMPERATURE      9 - supply air dry bulb temperature                   
        HUMIDITY         8 - supply air humidity ratio                         
        FLOW            11 - supply dry air mass flow rate                     
        TEMPERATURE     14 - interzone 1 air dry bulb temperature              
        HUMIDITY        13 - interzone 1 air humidity ratio                    
        FLOW            16 - interzone 1 dry air mass flow rate                
        TEMPERATURE     16 - interzone 2 air dry bulb temperature              
        HUMIDITY        15 - interzone 2 air humidity ratio                    
        FLOW            17 - interzone 2 dry air mass flow rate                
        FLOW            23 - extract dry air mass flow rate                    
        TEMPERATURE      1 - ambient dry bulb temperature                      
        HUMIDITY         1 - ambient humidity ratio                            
        FLOW            35 - leakage air mass flow rate (positive out)         
        TEMPERATURE     45 - equivalent "sol-air" outdoor temperature for room 
        TEMPERATURE     51 - equivalent "sol-air" outdoor temperature for plenu
        CONTROL         87 - fractional occupancy                              
        CONTROL         93 - fractional lighting heat gain                     
        CONTROL         99 - fractional equipment heat gain                    
        POWER           18 - heat gain from supply duct                        
        POWER           19 - heat gain from extract duct                       
        TEMPERATURE     15 - room temperature                                  
        TEMPERATURE     21 - room structure temperature                        
        TEMPERATURE     27 - plenum temperature                                
        TEMPERATURE     33 - plenum structure temperature                      
        HUMIDITY        14 - room humidity ratio                               

 2     OUTPUTS:
        TEMPERATURE     15 - room temperature                                  
        TEMPERATURE     21 - room structure temperature                        
        TEMPERATURE     27 - plenum temperature                                
        TEMPERATURE     33 - plenum structure temperature                      
        HUMIDITY        14 - room humidity ratio                               
        TEMPERATURE     39 - return temperature                                
        POWER            0 - sensible heat gains of room                       
        POWER            0 - sensible heat gains of plenum                     
        FLOW             0 - water vapour gains of room                        

 3     PARAMETERS:
           1.00000     room air capacity multiplier (-)                       
           50.0000     direct resistance room air node <-> ambient (K/kW)     
           3.89000     resistance room air node <-> room mass node (K/kW)     
           29.0000     resistance ambient <-> room mass node (K/kW)           
          0.100000E+12 direct resistance plenum air node <-> ambient (K/kW)   
           5.58000     resistance plenum air node <-> plenum mass node (K/kW) 
           81.8000     resistance ambient <-> plenum mass node (K/kW)         
           30.6000     resistance room air node <-> plenum air node (K/kW)    
           20800.0     capacitance of room mass node (kJ/K)                   
           677.000     capacitance of room air node (unmodified) (kJ/K)       
           10800.0     capacitance of plenum mass node (kJ/K)                 
           232.000     capacitance of plenum air node (kJ/K)                  
           48.0000     volume of room (m3)                                    
           13.0000     volume of plenum (m3)                                  
           0.00000     number of occupants (-)                                
           0.00000     lighting heat gain (kW)                                
           0.00000     fraction of lighting heat gain to extract air (-)      
           0.00000     equipment heat gain (kW)                               
           6.00000     zone number (parameter file=zoneN.par, n > 0) (-)      

 UNIT  72      TYPE 403
 Room with plenum and ducted return and interzone flows                  

 1     INPUTS:
        TEMPERATURE     10 - supply air dry bulb temperature                   
        HUMIDITY         9 - supply air humidity ratio                         
        FLOW            12 - supply dry air mass flow rate                     
        TEMPERATURE     15 - interzone 1 air dry bulb temperature              
        HUMIDITY        14 - interzone 1 air humidity ratio                    
        FLOW            17 - interzone 1 dry air mass flow rate                
        TEMPERATURE     11 - interzone 2 air dry bulb temperature              
        HUMIDITY        10 - interzone 2 air humidity ratio                    
        FLOW            18 - interzone 2 dry air mass flow rate                
        FLOW            24 - extract dry air mass flow rate                    
        TEMPERATURE      1 - ambient dry bulb temperature                      
        HUMIDITY         1 - ambient humidity ratio                            
        FLOW            36 - leakage air mass flow rate (positive out)         
        TEMPERATURE     46 - equivalent "sol-air" outdoor temperature for room 
        TEMPERATURE     52 - equivalent "sol-air" outdoor temperature for plenu
        CONTROL         88 - fractional occupancy                              
        CONTROL         94 - fractional lighting heat gain                     
        CONTROL        100 - fractional equipment heat gain                    
        POWER           20 - heat gain from supply duct                        
        POWER           21 - heat gain from extract duct                       
        TEMPERATURE     16 - room temperature                                  
        TEMPERATURE     22 - room structure temperature                        
        TEMPERATURE     28 - plenum temperature                                
        TEMPERATURE     34 - plenum structure temperature                      
        HUMIDITY        15 - room humidity ratio                               

 2     OUTPUTS:
        TEMPERATURE     16 - room temperature                                  
        TEMPERATURE     22 - room structure temperature                        
        TEMPERATURE     28 - plenum temperature                                
        TEMPERATURE     34 - plenum structure temperature                      
        HUMIDITY        15 - room humidity ratio                               
        TEMPERATURE     40 - return temperature                                
        POWER            0 - sensible heat gains of room                       
        POWER            0 - sensible heat gains of plenum                     
        FLOW             0 - water vapour gains of room                        

 3     PARAMETERS:
           1.00000     room air capacity multiplier (-)                       
           137.000     direct resistance room air node <-> ambient (K/kW)     
           1.14000     resistance room air node <-> room mass node (K/kW)     
           70.6000     resistance ambient <-> room mass node (K/kW)           
          0.100000E+12 direct resistance plenum air node <-> ambient (K/kW)   
           1.27000     resistance plenum air node <-> plenum mass node (K/kW) 
           200.000     resistance ambient <-> plenum mass node (K/kW)         
           9.47000     resistance room air node <-> plenum air node (K/kW)    
           10700.0     capacitance of room mass node (kJ/K)                   
           2030.00     capacitance of room air node (unmodified) (kJ/K)       
           16300.0     capacitance of plenum mass node (kJ/K)                 
           7030.00     capacitance of plenum air node (kJ/K)                  
           155.000     volume of room (m3)                                    
           43.0000     volume of plenum (m3)                                  
           0.00000     number of occupants (-)                                
           0.00000     lighting heat gain (kW)                                
           0.00000     fraction of lighting heat gain to extract air (-)      
           0.00000     equipment heat gain (kW)                               
           2.00000     zone number (parameter file=zoneN.par, n > 0) (-)      

 UNIT  73      TYPE 368
 Mixing of six moist air streams                                         

 1     INPUTS:
        TEMPERATURE     35 - Stream 1 dry bulb temperature                     
        HUMIDITY        10 - Stream 1 humidity ratio                           
        FLOW            19 - Stream 1 mass flow rate                           
        TEMPERATURE     36 - Stream 2 dry bulb temperature                     
        HUMIDITY        11 - Stream 2 humidity ratio                           
        FLOW            20 - Stream 2 mass flow rate                           
        TEMPERATURE     37 - Stream 3 dry bulb temperature                     
        HUMIDITY        12 - Stream 3 humidity ratio                           
        FLOW            21 - Stream 3 mass flow rate                           
        TEMPERATURE     38 - Stream 4 dry bulb temperature                     
        HUMIDITY        13 - Stream 4 humidity ratio                           
        FLOW            22 - Stream 4 mass flow rate                           
        TEMPERATURE     39 - Stream 5 dry bulb temperature                     
        HUMIDITY        14 - Stream 5 humidity ratio                           
        FLOW            23 - Stream 5 mass flow rate                           
        TEMPERATURE     40 - Stream 6 dry bulb temperature                     
        HUMIDITY        15 - Stream 6 humidity ratio                           
        FLOW            24 - Stream 6 mass flow rate                           

 2     OUTPUTS:
        TEMPERATURE     53 - Mixed air dry bulb temperature                    
        HUMIDITY        16 - Mixed air humidity ratio                          
        FLOW             0 - Mixed air mass flow rate                          

 3     PARAMETERS:
           0.00000     (dummy)                                                

 UNIT  74      TYPE 366
 Ideal heating of fluid stream                                           

 1     INPUTS:
        FLOW            29 - mass flow rate                                    
        TEMPERATURE     53 - inlet temperature                                 
        POWER            2 - rate of heat addition                             

 2     OUTPUTS:
        TEMPERATURE     54 - outlet temperature                                

 3     PARAMETERS:
           1.00000     fluid: 1 = air, any other value + water (-)            
           30.0000     time constant (s)                                      

 UNIT  75      TYPE  26
 CONTROL SIGNAL INVERTER                                                 

 1     INPUTS:
        CONTROL          1 - INPUT CONTROL SIGNAL                              

 2     OUTPUTS:
        CONTROL          0 - OUTPUT CONTROL SIGNAL                             

 3     PARAMETERS:
           0.00000     MULTIPLIER [DIMENSIONLESS]                             

 UNIT  76      TYPE  26
 CONTROL SIGNAL INVERTER                                                 

 1     INPUTS:
        CONTROL          1 - INPUT CONTROL SIGNAL                              

 2     OUTPUTS:
        CONTROL          0 - OUTPUT CONTROL SIGNAL                             

 3     PARAMETERS:
           0.00000     MULTIPLIER [DIMENSIONLESS]                             

 UNIT  77      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE      1 - temperature                                       

 2     OUTPUTS:
        CONTROL         60 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           30.0000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  78      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE      4 - temperature                                       

 2     OUTPUTS:
        CONTROL         61 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           30.0000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  79      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE     54 - temperature                                       

 2     OUTPUTS:
        CONTROL         62 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           30.0000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  80      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE      2 - temperature                                       

 2     OUTPUTS:
        CONTROL         68 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           30.0000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  81      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE     11 - temperature                                       

 2     OUTPUTS:
        CONTROL         70 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           300.000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  82      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE     12 - temperature                                       

 2     OUTPUTS:
        CONTROL         71 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           300.000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  83      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE     13 - temperature                                       

 2     OUTPUTS:
        CONTROL         72 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           300.000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  84      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE     14 - temperature                                       

 2     OUTPUTS:
        CONTROL         73 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           300.000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  85      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE     15 - temperature                                       

 2     OUTPUTS:
        CONTROL         74 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           300.000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  86      TYPE 301
 Temperature sensor                                                      

 1     INPUTS:
        TEMPERATURE     16 - temperature                                       

 2     OUTPUTS:
        CONTROL         75 - sensor output                                     

 3     PARAMETERS:
           0.00000     offset: input for zero output (C)                      
           1.00000     gain: change in input for 0->1 output (K)              
           300.000     time constant (s)                                      
           40.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  87      TYPE 303
 Flow rate sensor                                                        

 1     INPUTS:
        FLOW             2 - mass flow rate                                    

 2     OUTPUTS:
        CONTROL         63 - sensor output                                     

 3     PARAMETERS:
           2.00000     mass flow=1, vol flow=2, vel=3, vel pres=4 (-)         
           1.00000     air = 1, water = 2 (-)                                 
           1.00000     cross-sectional area of duct or pipe (m2)              
           0.00000     offset: input for zero output (sensed quantity)        
           1.00000     gain: change in input for 0->1 output (sensed quantity)
           1.00000     time constant (s)                                      
           20.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  88      TYPE 303
 Flow rate sensor                                                        

 1     INPUTS:
        FLOW            29 - mass flow rate                                    

 2     OUTPUTS:
        CONTROL         64 - sensor output                                     

 3     PARAMETERS:
           2.00000     mass flow=1, vol flow=2, vel=3, vel pres=4 (-)         
           1.00000     air = 1, water = 2 (-)                                 
           1.00000     cross-sectional area of duct or pipe (m2)              
           0.00000     offset: input for zero output (sensed quantity)        
           1.00000     gain: change in input for 0->1 output (sensed quantity)
           1.00000     time constant (s)                                      
           20.0000     upper limit of output range (-)                        
          -10.0000     lower limit of output range (-)                        

 UNIT  89      TYPE 305
 Static pressure sensor                                                  

 1     INPUTS:
        PRESSURE         5 - pressure                                          
        FLOW             2 - mass flow rate                                    

 2     OUTPUTS:
        CONTROL         65 - sensor output                                     

 3     PARAMETERS:
           1.00000     air = 1, water = 2 (-)                                 
           1.00000     cross-sectional area of duct or pipe (m2)              
           0.00000     offset: input for zero output (kPA)                    
           1.00000     gain: change in input for 0->1 output (kPA)            
           1.00000     time constant (s)                                      
           5.00000     upper limit of output range (-)                        
          -5.00000     lower limit of output range (-)                        

 UNIT  90      TYPE 302
 Humidity sensor                                                         

 1     INPUTS:
        HUMIDITY         1 - humidity ratio                                    
        TEMPERATURE      1 - temperature                                       

 2     OUTPUTS:
        CONTROL         66 - sensor output                                     

 3     PARAMETERS:
           1.00000     HR=1, RH=2, DP=3, WB=4, deg sat=5, spec enthalpy=6 (-) 
           0.00000     offset: input for zero output (sensed quantity)        
           1.00000     gain: change in input for 0->1 output (sensed quantity)
           30.0000     time constant (s)                                      
           1.00000     upper limit of output range (-)                        
           0.00000     lower limit of output range (-)                        

 UNIT  91      TYPE 302
 Humidity sensor                                                         

 1     INPUTS:
        HUMIDITY        16 - humidity ratio                                    
        TEMPERATURE     54 - temperature                                       

 2     OUTPUTS:
        CONTROL         67 - sensor output                                     

 3     PARAMETERS:
           1.00000     HR=1, RH=2, DP=3, WB=4, deg sat=5, spec enthalpy=6 (-) 
           0.00000     offset: input for zero output (sensed quantity)        
           1.00000     gain: change in input for 0->1 output (sensed quantity)
           30.0000     time constant (s)                                      
           1.00000     upper limit of output range (-)                        
           0.00000     lower limit of output range (-)                        

 UNIT  92      TYPE  26
 CONTROL SIGNAL INVERTER                                                 

 1     INPUTS:
        CONTROL          1 - INPUT CONTROL SIGNAL                              

 2     OUTPUTS:
        CONTROL          0 - OUTPUT CONTROL SIGNAL                             

 3     PARAMETERS:
           0.00000     MULTIPLIER [DIMENSIONLESS]                             

 UNIT  93      TYPE  26
 CONTROL SIGNAL INVERTER                                                 

 1     INPUTS:
        CONTROL          1 - INPUT CONTROL SIGNAL                              

 2     OUTPUTS:
        CONTROL          0 - OUTPUT CONTROL SIGNAL                             

 3     PARAMETERS:
           0.00000     MULTIPLIER [DIMENSIONLESS]                             
 Initial Variable Values:

 PRESSURE         1 ->     0.00000    (kPa)               
 PRESSURE         2 ->     0.00000    (kPa)               
 PRESSURE         3 ->     0.00000    (kPa)               
 PRESSURE         4 ->     0.00000    (kPa)               
 PRESSURE         5 ->     0.00000    (kPa)               
 PRESSURE         6 ->     0.00000    (kPa)               
 PRESSURE         7 ->     0.00000    (kPa)               
 PRESSURE         8 ->     0.00000    (kPa)               
 PRESSURE         9 ->     0.00000    (kPa)               
 PRESSURE        10 ->     0.00000    (kPa)               
 PRESSURE        11 ->     0.00000    (kPa)               
 PRESSURE        12 ->     0.00000    (kPa)               
 PRESSURE        13 ->     0.00000    (kPa)               
 PRESSURE        14 ->     0.00000    (kPa)               
 PRESSURE        15 ->     0.00000    (kPa)               
 PRESSURE        16 ->     0.00000    (kPa)               
 PRESSURE        17 ->     0.00000    (kPa)               
 PRESSURE        18 ->     0.00000    (kPa)               
 PRESSURE        19 ->     0.00000    (kPa)               
 PRESSURE        20 ->     0.00000    (kPa)               
 PRESSURE        21 ->     0.00000    (kPa)               
 PRESSURE        22 ->     0.00000    (kPa)               
 PRESSURE        23 ->     0.00000    (kPa)               
 PRESSURE        24 ->     0.00000    (kPa)               
 PRESSURE        25 ->     0.00000    (kPa)               
 PRESSURE        26 ->     0.00000    (kPa)               
 PRESSURE        27 ->     0.00000    (kPa)               
 PRESSURE        28 ->     0.00000    (kPa)               
 PRESSURE        29 ->     0.00000    (kPa)               
 PRESSURE        30 ->     0.00000    (kPa)               
 PRESSURE        31 ->     0.00000    (kPa)               
 PRESSURE        32 ->     39.0300    (kPa)               
 PRESSURE        33 ->     0.00000    (kPa)               
 PRESSURE        34 ->     38.1000    (kPa)               
 PRESSURE        35 ->     0.00000    (kPa)               
 PRESSURE        36 ->     26.8000    (kPa)               
 PRESSURE        37 ->     0.00000    (kPa)               
 PRESSURE        38 ->     57.0000    (kPa)               
 PRESSURE        39 ->     0.00000    (kPa)               
 PRESSURE        40 ->     42.5000    (kPa)               
 PRESSURE        41 ->     0.00000    (kPa)               
 PRESSURE        42 ->     15.6800    (kPa)               
 PRESSURE        43 ->     0.00000    (kPa)               
 PRESSURE        44 ->     3.29000    (kPa)               
 PRESSURE        45 ->     0.00000    (kPa)               
 FLOW             1 ->     0.00000    (kg/s)              
 FLOW             2 ->     0.00000    (kg/s)              
 FLOW             3 ->     0.00000    (kg/s)              
 FLOW             4 ->     0.00000    (kg/s)              
 FLOW             5 ->     0.00000    (kg/s)              
 FLOW             6 ->     0.00000    (kg/s)              
 FLOW             7 ->     0.00000    (kg/s)              
 FLOW             8 ->     0.00000    (kg/s)              
 FLOW             9 ->     0.00000    (kg/s)              
 FLOW            10 ->     0.00000    (kg/s)              
 FLOW            11 ->     0.00000    (kg/s)              
 FLOW            12 ->     0.00000    (kg/s)              
 FLOW            13 ->     0.00000    (kg/s)              
 FLOW            14 ->     0.00000    (kg/s)              
 FLOW            15 ->     0.00000    (kg/s)              
 FLOW            16 ->     0.00000    (kg/s)              
 FLOW            17 ->     0.00000    (kg/s)              
 FLOW            18 ->     0.00000    (kg/s)              
 FLOW            19 ->     0.00000    (kg/s)              
 FLOW            20 ->     0.00000    (kg/s)              
 FLOW            21 ->     0.00000    (kg/s)              
 FLOW            22 ->     0.00000    (kg/s)              
 FLOW            23 ->     0.00000    (kg/s)              
 FLOW            24 ->     0.00000    (kg/s)              
 FLOW            25 ->     0.00000    (kg/s)              
 FLOW            26 ->     0.00000    (kg/s)              
 FLOW            27 ->     0.00000    (kg/s)              
 FLOW            28 ->     0.00000    (kg/s)              
 FLOW            29 ->     0.00000    (kg/s)              
 FLOW            30 ->     0.00000    (kg/s)              
 FLOW            31 ->     0.00000    (kg/s)              
 FLOW            32 ->     0.00000    (kg/s)              
 FLOW            33 ->     0.00000    (kg/s)              
 FLOW            34 ->     0.00000    (kg/s)              
 FLOW            35 ->     0.00000    (kg/s)              
 FLOW            36 ->     0.00000    (kg/s)              
 FLOW            37 ->     0.00000    (kg/s)              
 FLOW            38 ->     0.00000    (kg/s)              
 FLOW            39 ->     0.00000    (kg/s)              
 FLOW            40 ->     0.00000    (kg/s)              
 FLOW            41 ->     0.00000    (kg/s)              
 FLOW            42 ->     0.00000    (kg/s)              
 FLOW            43 ->     0.00000    (kg/s)              
 FLOW            44 ->     0.00000    (kg/s)              
 FLOW            45 ->     0.00000    (kg/s)              
 FLOW            46 ->     0.00000    (kg/s)              
 TEMPERATURE      1 ->     25.0000    (C)                 
 TEMPERATURE      2 ->     20.0000    (C)                 
 TEMPERATURE      3 ->     20.0000    (C)                 
 TEMPERATURE      4 ->     20.0000    (C)                 
 TEMPERATURE      5 ->     20.0000    (C)                 
 TEMPERATURE      6 ->     20.0000    (C)                 
 TEMPERATURE      7 ->     20.0000    (C)                 
 TEMPERATURE      8 ->     20.0000    (C)                 
 TEMPERATURE      9 ->     20.0000    (C)                 
 TEMPERATURE     10 ->     20.0000    (C)                 
 TEMPERATURE     11 ->     20.0000    (C)                 
 TEMPERATURE     12 ->     20.0000    (C)                 
 TEMPERATURE     13 ->     20.0000    (C)                 
 TEMPERATURE     14 ->     20.0000    (C)                 
 TEMPERATURE     15 ->     20.0000    (C)                 
 TEMPERATURE     16 ->     20.0000    (C)                 
 TEMPERATURE     17 ->     20.0000    (C)                 
 TEMPERATURE     18 ->     20.0000    (C)                 
 TEMPERATURE     19 ->     20.0000    (C)                 
 TEMPERATURE     20 ->     20.0000    (C)                 
 TEMPERATURE     21 ->     20.0000    (C)                 
 TEMPERATURE     22 ->     20.0000    (C)                 
 TEMPERATURE     23 ->     20.0000    (C)                 
 TEMPERATURE     24 ->     20.0000    (C)                 
 TEMPERATURE     25 ->     20.0000    (C)                 
 TEMPERATURE     26 ->     20.0000    (C)                 
 TEMPERATURE     27 ->     20.0000    (C)                 
 TEMPERATURE     28 ->     20.0000    (C)                 
 TEMPERATURE     29 ->     20.0000    (C)                 
 TEMPERATURE     30 ->     20.0000    (C)                 
 TEMPERATURE     31 ->     20.0000    (C)                 
 TEMPERATURE     32 ->     20.0000    (C)                 
 TEMPERATURE     33 ->     20.0000    (C)                 
 TEMPERATURE     34 ->     20.0000    (C)                 
 TEMPERATURE     35 ->     20.0000    (C)                 
 TEMPERATURE     36 ->     20.0000    (C)                 
 TEMPERATURE     37 ->     20.0000    (C)                 
 TEMPERATURE     38 ->     20.0000    (C)                 
 TEMPERATURE     39 ->     20.0000    (C)                 
 TEMPERATURE     40 ->     20.0000    (C)                 
 TEMPERATURE     41 ->     25.0000    (C)                 
 TEMPERATURE     42 ->     25.0000    (C)                 
 TEMPERATURE     43 ->     25.0000    (C)                 
 TEMPERATURE     44 ->     25.0000    (C)                 
 TEMPERATURE     45 ->     25.0000    (C)                 
 TEMPERATURE     46 ->     25.0000    (C)                 
 TEMPERATURE     47 ->     25.0000    (C)                 
 TEMPERATURE     48 ->     25.0000    (C)                 
 TEMPERATURE     49 ->     25.0000    (C)                 
 TEMPERATURE     50 ->     25.0000    (C)                 
 TEMPERATURE     51 ->     25.0000    (C)                 
 TEMPERATURE     52 ->     25.0000    (C)                 
 TEMPERATURE     53 ->     20.0000    (C)                 
 TEMPERATURE     54 ->     20.0000    (C)                 
 TEMPERATURE     55 ->     6.00000    (C)                 
 TEMPERATURE     56 ->     6.00000    (C)                 
 TEMPERATURE     57 ->     20.0000    (C)                 
 TEMPERATURE     58 ->     80.0000    (C)                 
 TEMPERATURE     59 ->     80.0000    (C)                 
 TEMPERATURE     60 ->     80.0000    (C)                 
 TEMPERATURE     61 ->     80.0000    (C)                 
 TEMPERATURE     62 ->     80.0000    (C)                 
 TEMPERATURE     63 ->     80.0000    (C)                 
 TEMPERATURE     64 ->     20.0000    (C)                 
 TEMPERATURE     65 ->     20.0000    (C)                 
 TEMPERATURE     66 ->     20.0000    (C)                 
 TEMPERATURE     67 ->     20.0000    (C)                 
 TEMPERATURE     68 ->     20.0000    (C)                 
 TEMPERATURE     69 ->     20.0000    (C)                 
 TEMPERATURE     70 ->     20.0000    (C)                 
 TEMPERATURE     71 ->     20.0000    (C)                 
 TEMPERATURE     72 ->     20.0000    (C)                 
 TEMPERATURE     73 ->     20.0000    (C)                 
 TEMPERATURE     74 ->     20.0000    (C)                 
 TEMPERATURE     75 ->     20.0000    (C)                 
 CONTROL          1 ->     0.00000    (-)                 
 CONTROL          2 ->     0.00000    (-)                 
 CONTROL          3 ->    0.312000    (-)                 
 CONTROL          4 ->     0.00000    (-)                 
 CONTROL          5 ->     0.00000    (-)                 
 CONTROL          6 ->     0.00000    (-)                 
 CONTROL          7 ->     0.00000    (-)                 
 CONTROL          8 ->     0.00000    (-)                 
 CONTROL          9 ->     0.00000    (-)                 
 CONTROL         10 ->     0.00000    (-)                 
 CONTROL         11 ->     0.00000    (-)                 
 CONTROL         12 ->     0.00000    (-)                 
 CONTROL         13 ->     0.00000    (-)                 
 CONTROL         14 ->     0.00000    (-)                 
 CONTROL         15 ->     0.00000    (-)                 
 CONTROL         16 ->     0.00000    (-)                 
 CONTROL         17 ->    0.472000    (-)                 
 CONTROL         18 ->     1.00000    (-)                 
 CONTROL         19 ->     0.00000    (-)                 
 CONTROL         20 ->     0.00000    (-)                 
 CONTROL         21 ->     15.5000    (-)                 
 CONTROL         22 ->     0.00000    (-)                 
 CONTROL         23 ->     0.00000    (-)                 
 CONTROL         24 ->     0.00000    (-)                 
 CONTROL         25 ->     0.00000    (-)                 
 CONTROL         26 ->     0.00000    (-)                 
 CONTROL         27 ->     0.00000    (-)                 
 CONTROL         28 ->     0.00000    (-)                 
 CONTROL         29 ->     0.00000    (-)                 
 CONTROL         30 ->     0.00000    (-)                 
 CONTROL         31 ->     0.00000    (-)                 
 CONTROL         32 ->     0.00000    (-)                 
 CONTROL         33 ->     0.00000    (-)                 
 CONTROL         34 ->     0.00000    (-)                 
 CONTROL         35 ->     0.00000    (-)                 
 CONTROL         36 ->     0.00000    (-)                 
 CONTROL         37 ->     0.00000    (-)                 
 CONTROL         38 ->     0.00000    (-)                 
 CONTROL         39 ->     0.00000    (-)                 
 CONTROL         40 ->     0.00000    (-)                 
 CONTROL         41 ->     0.00000    (-)                 
 CONTROL         42 ->     0.00000    (-)                 
 CONTROL         43 ->     0.00000    (-)                 
 CONTROL         44 ->     0.00000    (-)                 
 CONTROL         45 ->     0.00000    (-)                 
 CONTROL         46 ->     0.00000    (-)                 
 CONTROL         47 ->     0.00000    (-)                 
 CONTROL         48 ->     0.00000    (-)                 
 CONTROL         49 ->     0.00000    (-)                 
 CONTROL         50 ->     0.00000    (-)                 
 CONTROL         51 ->     0.00000    (-)                 
 CONTROL         52 ->     0.00000    (-)                 
 CONTROL         53 ->     0.00000    (-)                 
 CONTROL         54 ->     0.00000    (-)                 
 CONTROL         55 ->     0.00000    (-)                 
 CONTROL         56 ->     0.00000    (-)                 
 CONTROL         57 ->     0.00000    (-)                 
 CONTROL         58 ->     0.00000    (-)                 
 CONTROL         59 ->     0.00000    (-)                 
 CONTROL         60 ->     0.00000    (-)                 
 CONTROL         61 ->     15.5000    (-)                 
 CONTROL         62 ->     0.00000    (-)                 
 CONTROL         63 ->     0.00000    (-)                 
 CONTROL         64 ->     0.00000    (-)                 
 CONTROL         65 ->     0.00000    (-)                 
 CONTROL         66 ->     0.00000    (-)                 
 CONTROL         67 ->     0.00000    (-)                 
 CONTROL         68 ->     0.00000    (-)                 
 CONTROL         69 ->     0.00000    (-)                 
 CONTROL         70 ->     22.2200    (-)                 
 CONTROL         71 ->     22.2200    (-)                 
 CONTROL         72 ->     22.2200    (-)                 
 CONTROL         73 ->     22.2200    (-)                 
 CONTROL         74 ->     22.2200    (-)                 
 CONTROL         75 ->     22.2200    (-)                 
 CONTROL         76 ->     0.00000    (-)                 
 CONTROL         77 ->     0.00000    (-)                 
 CONTROL         78 ->     0.00000    (-)                 
 CONTROL         79 ->     0.00000    (-)                 
 CONTROL         80 ->     0.00000    (-)                 
 CONTROL         81 ->     0.00000    (-)                 
 CONTROL         82 ->     0.00000    (-)                 
 CONTROL         83 ->     0.00000    (-)                 
 CONTROL         84 ->     0.00000    (-)                 
 CONTROL         85 ->     0.00000    (-)                 
 CONTROL         86 ->     0.00000    (-)                 
 CONTROL         87 ->     0.00000    (-)                 
 CONTROL         88 ->     0.00000    (-)                 
 CONTROL         89 ->     0.00000    (-)                 
 CONTROL         90 ->     0.00000    (-)                 
 CONTROL         91 ->     0.00000    (-)                 
 CONTROL         92 ->     0.00000    (-)                 
 CONTROL         93 ->     0.00000    (-)                 
 CONTROL         94 ->     0.00000    (-)                 
 CONTROL         95 ->     0.00000    (-)                 
 CONTROL         96 ->     0.00000    (-)                 
 CONTROL         97 ->     0.00000    (-)                 
 CONTROL         98 ->     0.00000    (-)                 
 CONTROL         99 ->     0.00000    (-)                 
 CONTROL        100 ->     0.00000    (-)                 
 OTHER            1 ->     0.00000    (-)                 
 OTHER            2 ->     0.00000    (-)                 
 POWER            1 ->     0.00000    (kW)                
 POWER            2 ->     0.00000    (kW)                
 POWER            3 ->     0.00000    (kW)                
 POWER            4 ->     0.00000    (kW)                
 POWER            5 ->     0.00000    (kW)                
 POWER            6 ->     0.00000    (kW)                
 POWER            7 ->     0.00000    (kW)                
 POWER            8 ->     0.00000    (kW)                
 POWER            9 ->     0.00000    (kW)                
 POWER           10 ->     0.00000    (kW)                
 POWER           11 ->     0.00000    (kW)                
 POWER           12 ->     0.00000    (kW)                
 POWER           13 ->     0.00000    (kW)                
 POWER           14 ->     0.00000    (kW)                
 POWER           15 ->     0.00000    (kW)                
 POWER           16 ->     0.00000    (kW)                
 POWER           17 ->     0.00000    (kW)                
 POWER           18 ->     0.00000    (kW)                
 POWER           19 ->     0.00000    (kW)                
 POWER           20 ->     0.00000    (kW)                
 POWER           21 ->     0.00000    (kW)                
 HUMIDITY         1 ->    0.400000E-02(kg/kg)             
 HUMIDITY         2 ->    0.400000E-02(kg/kg)             
 HUMIDITY         3 ->    0.400000E-02(kg/kg)             
 HUMIDITY         4 ->    0.400000E-02(kg/kg)             
 HUMIDITY         5 ->    0.400000E-02(kg/kg)             
 HUMIDITY         6 ->    0.400000E-02(kg/kg)             
 HUMIDITY         7 ->    0.400000E-02(kg/kg)             
 HUMIDITY         8 ->    0.400000E-02(kg/kg)             
 HUMIDITY         9 ->    0.400000E-02(kg/kg)             
 HUMIDITY        10 ->    0.400000E-02(kg/kg)             
 HUMIDITY        11 ->    0.400000E-02(kg/kg)             
 HUMIDITY        12 ->    0.400000E-02(kg/kg)             
 HUMIDITY        13 ->    0.400000E-02(kg/kg)             
 HUMIDITY        14 ->    0.400000E-02(kg/kg)             
 HUMIDITY        15 ->    0.400000E-02(kg/kg)             
 HUMIDITY        16 ->     0.00000    (kg/kg)             
 Simulation Error Tolerances:

 1      RTOLX=   0.100000E-03      ATOLX=   0.100000E-04
        XTOL=    0.200000E-03      TTIME=    1.00000    

 SUPERBLOCK 1
 2      FREEZE OPTION 0      SCAN OPTION 0

 SUPERBLOCK 2
 3      FREEZE OPTION 0      SCAN OPTION 0

 SUPERBLOCK 3
 4      FREEZE OPTION 0      SCAN OPTION 0

 SUPERBLOCK 4
 5      FREEZE OPTION 0      SCAN OPTION 0

 SUPERBLOCK 5
 6      FREEZE OPTION 0      SCAN OPTION 0

 SUPERBLOCK 6
 7      FREEZE OPTION 0      SCAN OPTION 0

 SUPERBLOCK 7
 8      FREEZE OPTION 0      SCAN OPTION 0

 SUPERBLOCK 8
 9      FREEZE OPTION 0      SCAN OPTION 0

 SUPERBLOCK 9
10      FREEZE OPTION 0      SCAN OPTION 0

 SUPERBLOCK10
11      FREEZE OPTION 0      SCAN OPTION 0
 The following are Boundary Variables in the simulation:


 SUPERBLOCK 1      REPORTING INTERVAL    300.000    
 CONTROL          1

 SUPERBLOCK 2      REPORTING INTERVAL    2.50000    
 CONTROL          1
 CONTROL          2
 CONTROL          3
 CONTROL         17
 CONTROL         18
 CONTROL         19
 CONTROL         20
 CONTROL         21
 CONTROL         22
 CONTROL         23
 CONTROL         24
 CONTROL         25
 CONTROL         26
 CONTROL         27
 CONTROL         77
 CONTROL         78
 CONTROL         79
 CONTROL         80
 CONTROL         81
 CONTROL         82

 SUPERBLOCK 3      REPORTING INTERVAL    2.50000    
 OTHER            1
 OTHER            2

 SUPERBLOCK 4      REPORTING INTERVAL    2.50000    
 PRESSURE         1
 PRESSURE         2
 PRESSURE         3
 PRESSURE         4
 PRESSURE         5
 PRESSURE         6
 PRESSURE         7
 PRESSURE         8
 PRESSURE         9
 PRESSURE        10
 PRESSURE        11
 PRESSURE        12
 PRESSURE        13
 PRESSURE        14
 PRESSURE        15
 PRESSURE        16
 PRESSURE        17
 PRESSURE        18
 PRESSURE        19
 PRESSURE        20
 PRESSURE        21
 PRESSURE        22
 PRESSURE        23
 PRESSURE        24
 PRESSURE        25
 PRESSURE        26
 PRESSURE        27
 PRESSURE        28
 PRESSURE        29
 PRESSURE        30

 SUPERBLOCK 5      REPORTING INTERVAL    2.50000    
 FLOW             1
 FLOW             2
 FLOW             3
 FLOW             4
 FLOW             5
 FLOW             6
 FLOW             7
 FLOW             8
 FLOW             9
 FLOW            10
 FLOW            11
 FLOW            12
 FLOW            13
 FLOW            14
 FLOW            15
 FLOW            16
 FLOW            17
 FLOW            18
 FLOW            19
 FLOW            20
 FLOW            21
 FLOW            22
 FLOW            23
 FLOW            24
 FLOW            25
 FLOW            26
 FLOW            27
 FLOW            28
 FLOW            29
 FLOW            30

 SUPERBLOCK 6      REPORTING INTERVAL    2.50000    
 TEMPERATURE      1
 TEMPERATURE      2
 TEMPERATURE      3
 TEMPERATURE      4
 TEMPERATURE      5
 TEMPERATURE      6
 TEMPERATURE      7
 TEMPERATURE      8
 TEMPERATURE      9
 TEMPERATURE     10
 TEMPERATURE     11
 TEMPERATURE     12
 TEMPERATURE     13
 TEMPERATURE     14
 TEMPERATURE     15
 TEMPERATURE     16
 TEMPERATURE     35
 TEMPERATURE     36
 TEMPERATURE     37
 TEMPERATURE     38
 TEMPERATURE     39
 TEMPERATURE     40
 TEMPERATURE     53
 TEMPERATURE     54

 SUPERBLOCK 7      REPORTING INTERVAL    2.50000    
 HUMIDITY         1
 HUMIDITY         2
 HUMIDITY         3
 HUMIDITY         4
 HUMIDITY         5
 HUMIDITY         6
 HUMIDITY         7
 HUMIDITY         8
 HUMIDITY         9
 HUMIDITY        10
 HUMIDITY        11
 HUMIDITY        12
 HUMIDITY        13
 HUMIDITY        14
 HUMIDITY        15
 HUMIDITY        16

 SUPERBLOCK 8      REPORTING INTERVAL    2.50000    
 CONTROL         65

 SUPERBLOCK 9      REPORTING INTERVAL    0.00000    

 SUPERBLOCK10      REPORTING INTERVAL    0.00000    